The User Manual of JAC200 Series General Frequency Converter
- 108 -
F7-14
Accumulated power consumption
Default value
-
Set range
0
~
65535 kwh
The accumulated power consumption of the frequency converter by far shall be displayed.
Group F8 Auxiliary functions
F8-00
Jog operation frequency
Default value
2.00Hz
Set range
0.00Hz
~
Maximum frequency
F8-01
Jog acceleration time
Default value
20.0s
Set range
0.0s
~
6500.0s
F8-02
Jog deceleration time
Default value
20.0s
Set range
0.0s
~
6500.0s
The given frequency and acceleration/deceleration time of the frequency converter shall be defined.
In jog operation, the start mode is permanently direct start mode (F6-00=0), and the stop mode is
permanently deceleration stop mode (F6-10=0).
F8-03
Acceleration time 2
Default value
Model dependent
Set range
0. 0s
~
6500.0s
F8-04
Deceleration time 2
Default value
Model dependent
Set range
0. 0s
~
6500.0s
F8-05
Acceleration time 3
Default value
Model dependent
Set range
0. 0s
~
6500.0s
F8-06
Deceleration time 3
Default value
Model dependent
Set range
0. 0s
~
6500.0s
F8-07
Acceleration time 4
Default value
Model dependent
Set range
0. 0s
~
6500.0s
F8-08
Deceleration time 4
Default value
Model dependent
Set range
0. 0s
~
6500.0s
JAC200 provides 4 groups of acceleration/deceleration time which are F0-17\F0-18 and above 3 groups of
acceleration/deceleration time
The definitions of 4 groups of acceleration/deceleration time are the same. Please see the relevant
description for F0-17 and F0-18
。
The 4 groups of acceleration/deceleration time can be selected alternatively through various combinations
of multifunctional digital input terminal DI. See the description for Function code F4-01
~
F4-05.
F8-09
Hopping frequency 1
Default value
0.00Hz