Applying the measuring-circuit
current
The UMG605US is designed for the connection
of ../1A and ../5A current transformers.
Only alternating currents, not direct currents,
can be measured via the current measurement
inputs.
Short-circuit all current transformer outputs
except one. Compare the currents displayed
by the UMG605US with the applied current.
Taking into account the current transformer
transformation ratio, the current displayed by
the UMG605US must correspond to the input
current.
The UMG605US must display approximately
zero Amperes in the short-circuited current
measurement inputs.
The current transformer ratio is set to 5/5A in
the factory and if necessary must be adapted
to the current transformer used.
Phase sequence
Check the direction of the voltage rotating
field in the measured value display of the
UMG605US.
A “right” rotating field usually exists.