12.13 Digital inputs/outputs
Your device has two digital outputs and two digital
inputs.
11 12 13
24V
DC
K1
K2
=
-
+
=
+
-
S1
S2
Digital Outputs
14 15 16
Digital Inputs
Fig:
Digital outputs and inputs
The inputs and outputs can be configured using
the GridVis® software included in the scope of
delivery.
12.13.1 Digital inputs
The digital inputs give you the option of having
information from other devices that have a digital
output sent directly to your device.
You can use the configuration window of the
GridVis® software in the Inputs area to define the
following for both digital inputs:
·Which value type the incoming signal has.
·Which scaling factor should be used for the
value.
Fig. Configuring inputs of the UMG via GridVis®
12.13.2 Pulse output
The digital outputs can also be used to output
pulses for counting energy consumption. To do
so, a pulse of defined length is applied to the out-
put after a certain, configurable amount of energy
has been reached.
To use a digital output as a pulse output requires
that various settings be made within the configu-
ration menu via the GridVis® software:
·Pulse width
·Digital output to be configured
·Output type (event message or S0 output)
·The measured value to be transmitted
·Pulse valency
Fig. Configuring digital outputs of the UMG via Grid-
Vis®
Содержание UMG 509-PRO
Страница 23: ...23 UMG 509 PRO www janitza com...
Страница 27: ...27 UMG 509 PRO www janitza com...
Страница 47: ...47 UMG 509 PRO www janitza com...
Страница 94: ...UMG 509 PRO 94 www janitza com Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report...
Страница 95: ...95 UMG 509 PRO www janitza com Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot...
Страница 107: ...107 UMG 509 PRO www janitza com 15 8 Dimensional drawings Fig Side view Fig Bottom view...
Страница 115: ...115 UMG 509 PRO www janitza com...