UMG 509-PRO
76
www.janitza.com
12.7 Failure monitoring (RCM)
The device enables continuous monitoring of the
connection to the residual current transformer for
inputs I5 and I6.
The failure monitoring can be activated via:
·The corresponding menu item, as described in
the section „11.3.1 Transformers“.
·Or by setting the addresses 18895 for the resid-
ual current measurement input I5 and 18897 for
I6.
If there is an interruption in the connection to
the current transformer, this status is recorded
in specific registers or displayed in the GridVis®
software.
Modbus
addr.
Value / Function
18895 (I5)
18897 (I6)
Failure monitoring for I5 / I6
0 = Deactivate monitoring
1 = Activate monitoring
Modbus
addr.
Value / Function
18907 (I5)
18908 (I6)
0 = Connection to residual current
transformer at I5 or I6 is fault-free
1 = Error in the current transformer
connection at I5 or I6
12.7.1
Alarm status
The bitwise coding within the alarm registers
(addr. 19224 for I5, 19225 for I6) makes it possible
to read out different alarm states:
Example:
unused
Alarm
Overcurrent
Warning
Bit:
0
15
0 0 0 0 0 0 0
14 13 12 11 10 9 8
0
7
0 0 0 0 0 0 0
6 5 4 3 2 1 0
Fig. Alarm register
An overcurrent was measured. The alarm bit is set
as well and must be acknowledged!
unused
Alarm
Overcurrent
Warning
Bit:
0
15
0 0 0 0 0 0 0
14 13 12 11 10 9 8
0
7
0 0 0 0 1 1 0
6 5 4 3 2 1 0
Fig. Example alarm register in the event of
measured overcurrent.
Warning:
The residual current has exceeded
the set warning limit value
Overcur-
rent:
The range has been exceeded
Alarm:
Alarm bit is set for: Warning or
overcurrent.
The alarm bit must be reset or
acknowledged manually.
Содержание UMG 509-PRO
Страница 23: ...23 UMG 509 PRO www janitza com...
Страница 27: ...27 UMG 509 PRO www janitza com...
Страница 47: ...47 UMG 509 PRO www janitza com...
Страница 94: ...UMG 509 PRO 94 www janitza com Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report...
Страница 95: ...95 UMG 509 PRO www janitza com Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot...
Страница 107: ...107 UMG 509 PRO www janitza com 15 8 Dimensional drawings Fig Side view Fig Bottom view...
Страница 115: ...115 UMG 509 PRO www janitza com...