User manual and technical data

Load Management Controller

 Procont

®

-LMC

Procont

®

-LMC-LITE

www

.janitza.de

Содержание Procont-LMC

Страница 1: ...3 Janitza electronics GmbH Vor dem Polst ck 6 35633 Lahnau Germany Support tel 49 6441 9642 22 info janitza de www janitza de User manual and technical data Load Management Controller Procont LMC Proc...

Страница 2: ...www janitza de 2 Procont LMC Procont LMC LITE Procont LMC Procont LMC LITE Load Management Controller Doc no 2 100 141 1 a 08 2023 The German version is the original edition of the documentation...

Страница 3: ...e and reflect the current state of the information available to us Nonetheless we wish to point out that updates of this document are not always possible at the same time as technical refinements are...

Страница 4: ...el 12 2 6 Warranty in the event of damage 12 3 Product description 14 3 1 Device description 14 3 2 Incoming goods inspection 14 3 3 Intended use 14 3 4 EU conformity declaration 14 3 5 Scope of deliv...

Страница 5: ...Lastkontrolle Load control 34 14 1 Sollwerte Setpoints 35 14 2 Max values 35 14 3 Main meter HZ 36 14 4 Div parameters 1 36 14 4 1 Hysteresis 36 14 4 2 Switching interval 36 14 4 3 LG reset 36 14 4 4...

Страница 6: ...48 21 2 Kontrollen und Momentanwerte Controls and instantaneous values 49 21 2 1 Alarme Alarms 49 21 2 2 Momentanwerte Instantaneous values 49 21 2 3 Load group state 50 21 2 4 Period view 50 21 2 5...

Страница 7: ...7 Procont LMC Procont LMC LITE 24 Technical data 59 24 1 Dimensional drawings 61 24 2 Connection diagram example of Procont LMC Procont LMC LITE 62 25 Maintenance and service 63 25 1 Maintenance 63 2...

Страница 8: ...e for the entire service life and pass it on to any possible subsequent users Find out about device revisions and the associat ed modifications of the usage information associ ated with your product a...

Страница 9: ...freight complete with accessories Observe special regulations for devices with built in batteries or rechargeable batteries Do not attempt to open or repair the device the component on your own becaus...

Страница 10: ...le risk of injury Be certain to observe all of the information listed under this symbol in order to avoid possible injury or even death 2 Safety 2 2 Hazard levels Warning and safety information is mar...

Страница 11: ...and warning notices in the documents that belong to the device 2 3 Product safety The device reflects current engineering practice and accepted safety standards but hazards can nonetheless arise Obser...

Страница 12: ...jury and material damage only electrically qualified personnel are permitted to work on the devices and their components mod ules assemblies systems and current circuits who have knowledge of The nati...

Страница 13: ...www janitza de 13 Procont LMC Procont LMC LITE...

Страница 14: ...extended periods of unfavor able conditions e g storage outside of the per missible climate thresholds without adjustment to the room climate condensation etc or transport stress e g falling from an...

Страница 15: ...a mains power failure Emergency stop curve Multi out linked outputs multi switch outputs multi timer timer Alarm processing e mail Eco controller function Tariff management 12 setpoints Self optimizat...

Страница 16: ...ps 4 Analog inputs measurement sensor and envi ronmental data 5 Serial interfaces RS 232 RS 232 485 6 Status LED inputs outputs LED on I O ac tive LED off I O inactive 7 Ethernet TCP IP 100BaseT 8 USB...

Страница 17: ...mware index Imprint manufacturer specif serial number Aux 100 240V 50 60Hz 9 15VA PROCONT LMC 6000300 10 2021 16 0f Aux 230V 50Hz 9VA PROCONT LMC 008 IO 6000303 10 2021 002 Aux 100 240V 50 60Hz 9 15VA...

Страница 18: ...f injury due to electrical voltage Severe bodily injury or death can result from Touching bare or stripped leads that are ener gized Device inputs that pose a hazard when touched Switch off your insta...

Страница 19: ...cture To protect your IT system network data com munications and measurement devices Inform your network administrator and or IT representative Always keep the meter firmware up to date and protect th...

Страница 20: ...2 HZ 0 00 kW 10 0m HT Wint Abg LG 0 Pressing the PROG button takes you to the se lection menu for the settings Use the keypad to select the desired settings and confirm with OK The following settings...

Страница 21: ...Synchronalarm Synchronization alarm Failure of the synchronization pulse 2 Maximalwertalarm Maximum value alarm Maximum value exceeded 3 Watchdog Alarm Watchdog alarm Internal error in the controller...

Страница 22: ...Moment Prio 0 Hptmss 00000 00 10 E 000 000 A 000 000 Instantaneous value alarm An alarm is output when a value is exceeded or not reached Parameters Function Hptmss I1 I2 Selection of an input source...

Страница 23: ...ched depending on the power the group that matches the power specified is always switched Stufen Levels Groups are switched from level 1 to level 8 Nullpunkt Zero point 0 10 kW A zero point that is us...

Страница 24: ...minutes A Display factor T Tariff Al all HAT main tariff NT low tariff Bez Designation Can only be changed via the software Impw Pulse value Valence of a pulse is indicated on the meter and must be mu...

Страница 25: ...for electronic load contactors Frequenz Frequency 0 25 Hz Var Takt Variable clock Blinken Output blinks Inv Output inverted The switching outputs can be programmed as normally open or normally closed...

Страница 26: ...G 001 Dig IO 5 Ausgang LG 001 LG 001 10 3 Pulse valency for external meters 10 00 00 MI 10 05 2022 HZ 0 00 kW 10 0m HT Wint Abg LG 0 10 00 00 MI 10 05 2022 HZ 0 00 kW 10 0m HT Wint Abg LG 0 Eingabeaus...

Страница 27: ...s or 2 each in parallel In the default setting the most important modules are already linked to the outputs 2 modules each in series All 4 modules in series Switch between the function modules using t...

Страница 28: ...pen Lastkontrolle TCP IP Einstellungen DHCP deaktiv Station Nr 1 FTPS aktiv TCP IP Einstellungen DHCP deaktiv Station Nr 1 FTPS aktiv TCP IP Adressen IP 192 168 0 50 Mask 255 255 255 0 GW 192 168 0 1...

Страница 29: ...Ethernet variant is particularly suitable for more remote meters that can be connected to the controller via the company network Proceed as follows to create a Modbus meter 1 Select meter and switch t...

Страница 30: ...er Tarife Tariffs T nur Hochtarif High tariff only nur Hochtarif High tariff only alle Tarife all tariffs HT NT Tariff selection Baudrate Bd 1 System System 300 2400 9600 19200 38400 Meter baud rate D...

Страница 31: ...eg Art Ctrl type Normal normal Regler Controller Controller type Selection of normal load group or controller Lstg power 5 0 kW 5 0 kW Connected load of the load group in kW SU Timer 1 2 3 128 Selecti...

Страница 32: ...e been set do not influence the timer and logical links do not influence the switching operations EE 0 0 m 0 0 m 99 9 m Minimum required switch on time in minutes This time specifies the period for wh...

Страница 33: ...ed back on The load program calculates the switch off time of the individual loads provided that min max times that have been set do not influence the timer and logical links do not influence the swit...

Страница 34: ...aktiv Gas ALS aktiv T1 0000 0 T2 0000 0 T3 0000 0 T4 0000 0 Z IO01 Hys 3 Gas ALS aktiv T1 0000 0 T2 0000 0 T3 0000 0 T4 0000 0 Z IO01 Hys 3 Div Parameter 1 Hysteresis 3 Schaltintervall 10 s LG Reset n...

Страница 35: ...ve and whether the 12 Sollwerte setpoints setting is activated The only default setting to be set is the setpoint HT Wi A maximum power limit can be activated to protect main fuses or supply lines fro...

Страница 36: ...end of the measuring period 14 4 4 12 setpoints Activates the 12 monthly setpoints A setpoint can be entered here for each month In addition each month can be divided into HT and NT 14 4 5 Div parame...

Страница 37: ...Load control value for the respective tariff T1 High tariff winter T2 Low tariff winter T3 High tariff summer T4 Low tariff summer Z IO1 IO1 IO12 Input from meter Hys 0 0 99 Hysteresis The possible n...

Страница 38: ...curve The emergency stop curve is used to switch off at a value above the normal switch off characteristic curve The emergency stop curve has the highest priority If it is exceeded load groups for whi...

Страница 39: ...10001 I 5 A 0 IP 192 168 0 51 UST 2 aktiv Modus TCP IP SP_0 Port 10001 I 5 A 0 IP 192 168 0 51 In a system with several controllers it makes sense to define one controller as the master con troller N...

Страница 40: ...larger Exceeded or undershot oder positive or negative value Hys 10 Hysteresis 10 E 5 Switch on delay 5 s A 5 Switch off delay 5 s W 000100 0 Limit value M Minimum running time in minutes Nr 1 RG 001...

Страница 41: ...0 Eingabeauswahl Master Ctrl Subst Lastkontrolle Schaltuhr Eingabeauswahl Master Ctrl Subst Lastkontrolle Schaltuhr Parameters Designation Nr 1 Up to 128 different timers can be set 001 The following...

Страница 42: ...on only 2 KNX EIB B 9600 baud Baud rate of output of the load group cir cuits for the EIB bus Sendeintervall Transmission interval 10 s 0 9999 s Read write interval HptGr 10 Main group 0 15 MittlGr 0...

Страница 43: ...9200 38400 115200 baud Baud rate 2 ModbRTU The station is configured as a Modbus slave B 9600 baud 2400 9600 19200 38400 115200 baud Baud rate Adresse Address 1 1 255 Controller address Data 8 N 1 8N1...

Страница 44: ...HZ 0 00 kW 10 0m HT Wint Abg LG 0 10 00 00 MI 10 05 2022 HZ 0 00 kW 10 0m HT Wint Abg LG 0 Eingabeauswahl Schaltuhr Schnittstellen Sondertage Eingabeauswahl Schaltuhr Schnittstellen Sondertage Up to 2...

Страница 45: ...Modbus server E Sperre Lock no ja yes active no input possible nein no deactivated input possible Activate input lock Ben Anmeldung User login yes yes no User login via Procont Vis TCP Error Reset no...

Страница 46: ...ktiv 20 1 Synchronisation Synchronization Ausl s extern Trigger external IO01 Parameters Default Setting Description 1 extern external Here the synchronization is done externally e g IO01 IO02 P Dauer...

Страница 47: ...chtarif High tariff only Hoch Niedt High and low tariff Somm und Wint Summer and winter tariff HT NT So Wint High tariff Low tariff Summer and Winter tariff Verz gerung 0 s Delay of tariff switching i...

Страница 48: ...igital I O 1 Art I Fkt Z 0 Eco Regler 7 P 0 000 N 0 000 R1 4 0 0 0 0 R5 8 0 0 0 0 RG001 0 1 12 Ix 0 MW 0 0 Regl 0 Dyn 0 Out 0 Zt 5 0 0 RG001 0 1 RG001 0 1 12 12 Ix 0 MW 0 0 Regl 0 Dyn 0 Out 0 Zt 5 0 0...

Страница 49: ...int is exceeded Always select max value to be higher than the setpoint Kr 8 94 Tr 0 00 Mx 0 00 mM 0 00 P 0 00 Re 36 59 Pm 0 00 Ku 0 00 Kr 8 94 Tr 0 00 Mx 0 00 mM 0 00 P 0 00 Re 36 59 Pm 0 00 Ku 0 00 S...

Страница 50: ...hed off E2 Switch on characteristic curve 2 if the trend value falls below this value the consumers are switched on 21 2 3 Load group state Status display of the individual load groups A bar is displa...

Страница 51: ...on Dyn 0 Out 0 Limit value Zt 5 0 0 Times Response time s Reset delay s Minimum run time s 21 2 8 Analog inputs Analog AI 1 13 Analog input 1 Art passiv ADC 1023 MoW 24 1 C Analog AI 1 Analog AI 1 13...

Страница 52: ...of charging station storage In AL Alarm SU Timer RG Control EC Eco controller LG Load group DA Digital output IO input output EX IC DE FM M A automatic read from charging station M manual selection m...

Страница 53: ...000 Zst IO 2 kWh T1 0 000 T2 0 000 T3 T4 0 000 Zst IO 2 kWh T1 0 000 T2 0 000 T3 T4 0 000 21 3 1 Zustand State The consumptions of the individual inputs are displayed here Imp Pulses kWh Kilowatt hou...

Страница 54: ...ption for the year up to the present time MVb IO 3 Imp T1 0 000 MVb IO 3 Imp MVb IO 3 Imp T1 0 000 MVb IO 1 Imp T1 0 000 MVb IO 1 Imp T1 0 000 MVb IO 2 Imp T1 0 000 T2 0 000 T3 T4 0 000 MVb IO 2 Imp T...

Страница 55: ...rrect if necessary Check device and replace if necessary Dupline Analink Communication error to the devices bus error Check cable connections check bus settings on the controller and on the expansion...

Страница 56: ...adapter network settings on page 28 Antivirus Firewall blocked Create exception rule for Procont Vis exe Sub meter e g from the utility company Meter value is incorrect Pulse valency set incorrectly C...

Страница 57: ...0 MI 10 05 2022 HZ 0 00 kW 10 0m HT Wint Abg LG 0 10 00 00 MI 10 05 2022 HZ 0 00 kW 10 0m HT Wint Abg LG 0 Eingabeauswahl Alarmeinstellungen Eco Regler Ein Ausg nge Eingabeauswahl Alarmeinstellungen E...

Страница 58: ...f one of the two devices was not configured or not configured correctly 3 The IP interface of one of the devices is defec tive please send the device in Why does the controller switch off the load gro...

Страница 59: ...ontal Installation mounting suitable DIN rail 35 mm 1 38 in TS 35 7 5 according to EN 60715 12TE LCD graphic design 40 x 20 mm Environmental conditions during operation The device Is for weather prote...

Страница 60: ...S3 Screw terminals D D GND Protocol and transmission rate Synch gateway 300 2400 9600 19200 38400 baud Modbus server 300 2400 9600 19200 38400 baud Bus master 300 2400 9600 19200 38400 baud Terminal c...

Страница 61: ...www janitza de 61 Procont LMC Procont LMC LITE 24 1 Dimensional drawings Front view Procont LMC Procont LMC LITE Side view Procont LMC Procont LMC LITE All dimensions in mm...

Страница 62: ...www janitza de 62 Procont LMC Procont LMC LITE 24 2 Connection diagram example of Procont LMC Procont LMC LITE PROCONT LMC...

Страница 63: ...f you have any further questions please contact us directly We request the fol lowing information to ensure faster pro cessing of your questions Device designation see rating plate Serial number see r...

Страница 64: ...ject to technical alterations The current version of the document can be found in the download area at www janitza de Janitza electronics GmbH Vor dem Polst ck 6 35633 Lahnau Germany Tel 49 6441 9642...