20
www.janitza.de
Procont
®
-LMC-008-IO
9. Alarms on the display
States of the alarms.
Pending alarms can be acknowledged using
"ENT" (Enter). To do so, press the joystick to the
right for 1.5 seconds.
1.5 sec
If the alarm is still displayed after acknowledging
and the fault is no longer present, switch off the
controller for 5 minutes. After switching on, the
alarm will no longer be displayed.
Alarme (Alarms):
Alles OK (All OK)
Alarme (Alarms):
Alles OK (All OK)
Pending alarms; alarms that have already been
acknowledged but are still active are also dis-
played here.
Alarm
Error
Ext.Bus
Bus failure of a bus device
Not-Aus
(Emergency stop)
Emergency stop alarm. Emergency stop curve exceeded.
TCP-Mod.
TCP module alarm. The TCP module had an internal error. Please acknowledge.
MAN-Sch.
(Manual switch)
Consumer manual switch active. This alarm is displayed when one or more toggle
switches have been pressed to "ON".
Watchdog
A watchdog alarm was triggered due to an internal program cycle error. A restart
was performed.
File-Al
File error alarm. One or more fi les on the SD memory card are corrupt.
Daten-Al (Data Al)
Data from Procont
®
master station not received
SNTP-Uhr
(SNTP clock)
Connection to SNTP time server failed
UST-Al
(substation alarm)
Substation alarm. Connection to one or more substationsfailed