UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
www.janitza.de
34
10. Analog outputs
The device has 1 passive analog output which
can deliver a current of 0 - 20 mA. An external
power supply unit (24 V DC) is required for oper-
ation.
The connectable load must not exceed a resis-
tance of 300 ohms.
If the analog output is loaded with a higher resis-
tance, the output range (20 mA) is restricted.
The measured value assigned to the analog out-
put, the start and end values and the output range
4 - 20 mA
or
0 - 20 mA
must be set using the
GridVis
®
software (for more information, refer to
section „13.14 Configuration of the analog output“
on page 64)
230 VAC
24 VDC
+
-
26
25
Analog output 1
+
Analog inputs
UMG 96-PA
External
operating voltage
+
-
=
Fig.
Analog output connection