Module 96-PA-RCM / 96-PA-RCM-EL
Fig. Window Measurement > Module mode “Residual
current”
B
1
2
3
4
Fig. “Residual current” window display, with the
settings of the parameters for the residual current
measuring modes.
No.
Residual current
parameters
Settings
1
Analog CH 1
type,
I5 terminal 29/30
Suitable transformer types:
·AC (0 .. 30 mA
rms
)
·0 .. 20 mA
·4 .. 20 mA
2
Analog CH 2
type,
I6 terminal 31/32
Suitable transformer types:
·AC (0 .. 30 mA
rms
)
·0 .. 20 mA
·4 .. 20 mA
3
Transformer
ratios
Current transformer:
·CH 1 - prim. and sec.
·CH 2 - prim. and sec.
4
Cable break
detection
Configurable in the GridVis
®
software and in the Modbus
editor (basic device).
Tab. Settings options in the residual current module mode
9.2 Module mode
The
Module mode
item in the
Measurement
win-
dow is for switching the measurement modes:
1.
Residual current
or
2.
DC power.
1. Module mode
Residual current
·Use buttons 3/4 (
“
”/“
”
) to select the item
Module mode
and confirm with button 6
Enter.
·The measuring mode set is displayed in yellow
(default setting
Residual current
).
·If necessary, use buttons 3/4 (
“
”/“
”
) to select
the item
Residual current
and confirm with but-
ton 6
Enter
.
·Afterwards, in the
Measurement
window, select
the item
Residual current
and confirm with but-
ton 6,
Enter
.
·The window
Display “Residual current”
appears
with the parameters to be set:
2. Module mode
DC power
·Use buttons 3/4 (
“
”/“
”
) to select the item
Module mode
and confirm with button 6
Enter.
·The measuring mode set is displayed in yellow.
·Use buttons 3/4 (
“
”/“
”
) to select the item
DC
power
and confirm with button 6
Enter
.
Fig. Window Measurement > Module mode “DC power”
·Afterwards, in the
Measurement
window, select
the item
DC power
.
·To enter the
Display
window with the parameters
for the
DC power
measurement mode to be set,
press button 6
Enter
.