EVO controller

 

Manual 

www.jakkagroup.com

 

14 

Tr (return)

ko

The return air temperature sensor works properly

Problem with the return air temperature sensor:

check electrical connections of the temperature probe (see wiring diagram);

1) 

2) if the problem is not solved, replace the temperature probe
3) if the problem is not solved, replace the electronic card.

ok

Tx (expelled)         

ko

The exhaust air temperature sensor works properly

Problem with the expelled air temperature sensor:

1)

1) check electrical connections of the temperature probe (see wiring diagram
2) if the problem is not solved, replace the temperature probe
3) if the problem is not solved, replace the electronic card.

Ti (input)

ko

The input air temperature sensor works properly

Problem with the input air temperature sensor:
1) check electrical connections of the temperature probe (see wiring diagram);
2) if the problem is not solved, replace the temperature probe
3) if the problem is not solved, replace the electronic card.

Tw (water)             

ko

Problem with the water-powered battery temperature sensor:

1) check electrical connections of the temperature probe (see wiring diagram);

2) if the problem is not solved, replace the temperature probe
3) if the problem is not solved, replace the electronic card.

Filters

ok

Clean filters

ko

Clogged filters: replace filters. If the filters alarm is based on the machine     

operation hours, you must reset the Filter Hours parameter (Installer menu)

Fans

CO

2

 VOC 

RH sensor

Tw (water) low

ok

The temperature of the water from the battery is higher than a safety 
threshold, there is no risk of water freezing in the battery

ok

ok

ok

It is present only if the air after-treatment control is equipped with a water 
powered battery (Factory menu)

The water coil temperature sensor works properly

ko

Risk of liquid freezing in the water-powered battery

It is present only if the air after-treatment control is equipped with a water coil 
(Factory menu)

 It is present only if the fan status alarm is configured with differential 
 pressure switch, with tachometric signal of fans or with fan Digital Output 
 (Factory menu)

Fans OK

Possible failure of the fans

 It is present only if the fan speed automatic control is configured with a 
 CO

2

 o CO

2

-VOC sensor (Installer menu)

Probe OK

Possible failure of the probe or of the connector

It is present only if the fan speed automatic control is configured with a 
relative humidity sensor (Installer menu)

Probe OK

Possible failure of the probe or of the connector

It is present only if the filter status alarm with differential pressure switch is 
configured or is based on the machine operation hours (Factory menu)

ok

ko

ok

ko

ok

ko

Содержание EVO PH

Страница 1: ...Manual EVO PH and EVO D PH IP Heat recovery unit controller JAK KA GROUP december 2019 www jakkagroup com J 8 Г ...

Страница 2: ...svih informacija u katalozima uputstvima i cenovnicima bez prethodne najave Content Main Window 2 Fan Speed Control at constant flow or pressure 2 Booster function 3 Air Post Treatment Control 4 Set point temperature 4 Post heating control 5 Menu selection window 5 Status menu operating status 6 Program menu weekly program control 9 Default 10 Time table 10 Setting speed levels 12 Menu clock 12 Al...

Страница 3: ...ressing the center button it automatically disappears by pressing the arrow keys In detail the possible options are as follows off fans are motionless with this option but watch out that the unit is live anyway this value is achieved by going below the minimum speed value that can be set xxx if the unit is equipped with continuously variable speed fans a fan speed percentage flow or a full scale p...

Страница 4: ...is obtained by selecting a greater value than clock xxx m h if the unit is in constant flow version CAV with kit the desired value can be set in m3 h of flow Fans will automatically run at the speed corresponding to this flow according to the change in the load xxx Pa if the unit is in constant pressure version COP with kit the desired value can be set in pascal of pressure Fans will automati call...

Страница 5: ... The temperature set point is given by the thermometer icon located at the bottom right of the screen like images next paragraph that can be red heat mode or blue cooling mode When the bottom icon is selected the desired interior temperature set point Ts function is accessed the user can increase the Ts value by the up arrow key or vice versa reduce it by the down arrow key With the central button...

Страница 6: ... and press it In addition to post heating the EVO PH control can run an electric pre heating system to prevent the formation of ice in the heat exchanger The control starts the anti frost procedure automatically when the temperature detected by the expelled probe Tx drops below 3 C The heater is powered at the minimum power if the Tx temperature keeps dropping the pre heater power is increased ste...

Страница 7: ...ation Display of the Status menu with fan speed In order to display the status of one unit you must select this unit move by means of the arrow keys and confirm your selection by pressing OK If the control is configured to run one unit when this menu is accessed the status of this unit can be seen right away and the values of the characterizing parameters are displayed all parameters can be scroll...

Страница 8: ... probe is present it indicates the percentage relative humidity value detected by the probe It can take values between 0 and 100 It is on if the automatic operation of fans is configured through a 0 10V external signal It indicates the percentage value of the external signal 10V corresponds to 100 It is on if one digital input DI is configured as remote this parameter can be set in the factory Off...

Страница 9: ...xt one of the digital input factory off the contact is open standard management air on the contact is closed fan extraction turned off fan supply run at speed set The digital input output can be programmed from the factory menu requiring password to the constructor and instructions about the functions available Fire PFanSupply PFanExhau Recircul Req Off On Dehumidif Off On DWat NoFrost Off On Td D...

Страница 10: ... m3 h for constant flow machines with kit Moreover the air after treatment if available can be enabled disabled in a different way for each day of the week by time period 1 to 8 time periods that can be defined by the user in 30 minute steps To access the program control functions select the Program item by the arrow keys highlight it and press OK PROGRAM MENU WEEKLY PROGRAM CONTROL Program menu w...

Страница 11: ...probe or is controlled through a 0 10V external signal 20000 m h if it is a constant flow unit with cop cav kit This value also depends on the settings in the factory menu based on the performance of the unit 1000 Pa if it is a constant pressure unit with cop cav kit This value also depends on the settings in the factory menu based on the performance of the unit cop cav kit This value also depends...

Страница 12: ...hange the time period you are working on without returning to the previous page by selecting this line and pressing OK scroll the several time periods 1 8 using the arrow keys and just press OK when you reach the desired period Time hh mm set the starting time of the current time period by selecting this line and pressing OK the arrows keys increase up arrow or decrease down arrow the time by 30 m...

Страница 13: ...uality or relative humidity probe or controlled through a 0 10V external signal the fan speed will be automatically controlled by one of these devices It can be reached by pressing the up arrow for a few seconds auto is above the maximum speed value that can be set xxx m3 h if the unit is in constant flow version with kit the desired value can be set in m3 h of flow Xxx Pa if the unit is in consta...

Страница 14: ...ommunication ok Te external ko The external air temperature sensor works properly Problem with the external air temperature sensor 1 check electrical connections of the temperature probe see wiring diagram 2 if the problem is not solved replace the temperature probe 3 if the problem is not solved replace the electronic card ok Configuration ko ok The configuration of the digital input is ok ko The...

Страница 15: ...place the electronic card Filters ok Clean filters ko Clogged filters replace filters If the filters alarm is based on the machine operation hours you must reset the Filter Hours parameter Installer menu Fans CO2 VOC RH sensor Tw water low ok The temperature of the water from the battery is higher than a safety threshold there is no risk of water freezing in the battery ok ok ok It is present only...

Страница 16: ...y if the machine is in the constant flow version with control on both flows The return pressure sensor works properly Dp ko Possible anomaly of the pressure sensor ok It is present only if the machine is in the constant pressure version with control on one flow The pressure sensor works properly It is present only if the fan speed automatic control alarm is configured with a CO2 o CO2 VOC sensor I...

Страница 17: ...dify In order to enter the password press the down arrow key the line where the password must be entered is highlighted Press OK Select the desired value for the first digit using the up down arrow keys and press OK when you reach the desired value Repeat this operation for the three remaining figures If you have entered the correct password the installer menu is displayed otherwise if the passwor...

Страница 18: ...anguage SI Slovenian language Auto1 2 With this parameter you can configure a device that automatically adjusts the fan speed See the wiring diagram for the connection of the device External signal The fan speed will be controlled through an external 0 10V analog signal default value if the external signal takes the 0V value the control will indicate a problem with the source of the external signa...

Страница 19: ...ontrolled by a CO2 or CO2 VOC sensor with a 0 10V output and will have a linear trend between 0 and 2000 ppm 0V corresponds to 0 ppm and 10V corresponds to 2000 ppm if the external signal of the CO2 sensor takes the 0V value the control will display a problem with the sensor For a unit equipped with adjustable speed fans Where AutoMin ppm corresponds to the CO2 CO2 VOC concentration for which the ...

Страница 20: ...mage of the auto ext signal parameter after fixing the SP 1 2 and SP 2 3 values the nominal values at which speed changes from 1 to 2 and from 2 to 3 the correct value to be assigned to the parameter can be obtained as follows AutoMin 7 x SP 1 2 2 x SP 2 3 5 AutoMax 8 x SP 2 3 3 x SP 1 2 5 AutoMin ppm 7 x SP 1 2 2 x SP 2 3 5 AutoMax ppm 8 x SP 2 3 3 x SP 1 2 5 AutoMax ppm This parameter is only av...

Страница 21: ...tting the parameter to yes you must enter the code in the installer menu access screen to make changes to the sets The time available for modifies is 5 minutes elapsed this password must be entered again cità minima INT VE percentage of exhaust fan speed vs input fan see next paragraph INTECCESSO rounds up to the next integer VMIN minimum speed set in the Factory menu step discrete values of the s...

Страница 22: ...of the solenoid valve 3 points it is adjustable in 10 second steps Pir Min 001 240 This parameter is available if one digital input is configured at the PIR value presence detector see Factory menu Default value 10 it is expressed in minutes it is the time during which the fans run at the maximum speed after the pulse closing of a NO contact from a presence detector After this lapse the fans will ...

Страница 23: ... browser and type http 192 168 1 243 or the address modified in the address bar MODBUS RTU Baud Rate 9600 bit s 1 stop bit parity even disconnection after 10 sec without access to the registers modifiable via MODBUS close jumper on rs485 card insert if the unit is at the end of bus line It is available a version of touch panel which support protocol Modbus Tcp ip or Modbus RTU by an additional car...

Страница 24: ...directly post heat fans or timer Changes are automatically saved after 5 seconds The writing of the Holding Registers via modbus is disabled for 60 seconds after each change made through the Web server In order for the webpage to be continuously updated click the refresh on key the writing will become refresh off so the page will be updated every five seconds Should the machine be equipped with a ...

Страница 25: ...OLD UNIT3 HOUR FILTERS ALARM THRESHOLD UNIT4 UNIT_2_M AX_FILT HOURS UNIT_3_M AX_FILT HOURS UNIT_4_M AX_FILT HOURS SPEED_SE T_POINT B00 R W DEVICE_RESET 1 RESET B01 R TERMINAL_ACTIVE 1 ACTIVE B04 R W CONNECTION_LOST 1 LOST B13 R W CMD DEVICE RESET 1 RESET B14 R W WR_APP_CONF 1 WRITE PENDING B15 R W WR_SP 1 WRITE OENDING DISCONNECTION HAS TAKEN PLACE DEFAULT 0 IF SET AT 1 THE CARD IS RESET ENABLE BI...

Страница 26: ...LURE INPUT PROBE LINE FAILURE TEMPERATURE SET_POINT TIMER SPEEDS REMOTE CONTROL INPUT AIR TEMPERATURE WATER TEMPERATURE SUPPLY FAN INDIPENTENTLY CONTROL ENABLE B00 BY PASS B01 SUPPLY_SPEED_REM_CONT_ACTIVE B02 EXHAUST_SPEED_REM_CONT_ACTIVE B03 DEHUM_OM B04 NOFROST_ACTIVE B05 EXT_DI_HUMIDITY B06 EXT_DI_PIR_MIN B07 EXT_DI_REMOTE_OFF B08 HEAT_1 B09 HEAT_2 B10 TEMP_WATER_LOW B11 EXT_DI_SUMMER B12 EXT_D...

Страница 27: ...IR TEMPERATURE AFTER COOL COIL IN DEUMIDIFY SYSTEM COMMUNICATION ERROR IN X531 BOARD WATER COIL FROST ALARM AIR HUMIDITY QUALITY PROBE TIMEOUT ALARM COMMUNICATION ERROR IN X570 BOARD DELIVERY COMMUNICATION ERROR IN X570 BOARD EXHAUST DELIVERY PRESSURE SENSOR FAILURE EXHAUST PRESSURE SENSOR FAILURE R R R R R R R R R R R R R W R W 1001 1002 1003 TIME_TABLE_SPEED_0 TIME_TABLE_SPEED_1 TIME_TABLE_SPEED...

Страница 28: ...anel INSTALLATION CONTROL PANEL WIRING Connection Tcp ip Rs485 additional card Remote panel rear view SERVICE DATA Connect the power supply to the 24V and G terminals matching the correct polarity Connect the BUS to the S terminal Using a min 0 3 mm2 section shielded cable is recommended In case of communication errors check the connections between the remote panel and the electronic card For pane...

Страница 29: ...uded The manufacturer also waives any liability for subsequent damages Goods that are claimed to be defective must be shipped to the manufacturer through the dealer together with a detailed description of the fault written by the dealer Shipment cost will be charged to the customer The manufacturer shall bear the cost of returning the repaired goods In no case will the manufactu rer be responsible...

Страница 30: ... jakkagroup com MOUNTING mm Insert two sticks in the left and the right of the touch panel Insert bottom touch panel in the support Press the support up and the touch panel down then insert also the top touch panel in the support ...

Страница 31: ...11 2 600 901 faks 381 0 11 2 600 906 web www jakkagroup com e mail jakkagroup jakkagroup com JAK KA GROUP CRNA GORA adresa V Crnogorske brigade 3 85347 Igalo Crna Gora telefon 382 0 31 330 285 faks 382 0 31 330 285 mobilni 382 0 69 517 008 web www jakkagroup com e mail technoclima mare t com me ...

Отзывы: