The JA-180S wireless fire detector 

 

MHS53800 

1

The JA-180S wireless fire detector

This device is designed to detect the presence of fire inside residential or 

commercial buildings. It should not be installed in industrial premises. The 
battery-powered detector has a built-in local warning siren combined with a 
red LED indicator. Alarm information can also be transferred via a wireless 
connection to Jablotron systems.  

The JA-180S detector combines an optical smoke sensor with a heat 

sensor. Both sensors have their outgoing signals processed digitally, resulting 
in higher false alarm immunity. The optical sensor works using a light diffusion 
principle and is very sensitive to the presence of large-sized particles which 
are characteristic of dense smokes. By contrast, the sensor is less sensitive to 
small-sized particles which are typical of cleanly burning fires. In particular, the 
smoke sensor is not capable of detecting the by-products of cleanly-burning 
fluids such as alcohols, for instance. This deficiency is compensated for by the 
built-in heat sensor. This sensor provides a slower reaction when compared to 
the smoke sensor, but is much better at reacting to fires with rapidly rising heat 
producing only a little smoke. 

Smoke / heat sensor participation is configurable by jumper-settings.  

Detection range, detector positioning 

The smoke detector must be installed so that any smoke easily drifts 

into the detector, such as on the ceiling. It is suitable for residential 
buildings, but not suitable for free spaces or an outdoor environment. 
However, the detector is not suitable for installation in outdoor spaces or 
interiors with an extremely high ceiling (more than 5 m) where fire by-products 
would not reach the detector position. The detector must always be placed 
in the section leading to the exit of the apartment (escape route), see 
Figure 1. If the apartment has a floor area greater than 150 m

2

, an 

additional detector is required in the apartment, see Fig.2. An 
apartment block must be equipped with a detector in each apartment. 
In family houses and residential flats or maisonettes a detector must 
also be placed at the highest point of common hallways or spaces 
(escape routes), see Fig.3. 

KITCHEN

MINIMUM SECURITY

FOR MORE SECURITY

LIVING ROOM

BEDROOM

BEDROOMS

Fig. 1 

BEDROOMS

BEDROOM

BEDROOM

LIVING ROOM

KITCHEN

MINIMUM SECURITY

FOR MORE SECURITY

Fig. 2 

It is recommended to place 

additional detectors in rooms 
where people sleep or in rooms 
with an increased risk of fire, see 
Fig.2.  

Positioning on level ceilings

Place the detector in the center 

of the room, as level as possible. 
Detectors must not be recessed 
into the ceiling (worse conditions 
for the spread of smoke). Never 
place the detector in a room 
corner (ensure a distance of at 
least 0.5 meters from the corner), 
see Fig 4

.

BED

ROOM

KITCHEN

MINIMUM SECURITY

BED

ROOM

BED

ROOM

Fig. 3 

x

   Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Figure 5. 

0.5m

CEILING

BEST LOCATION

(CENTRE OF CEILING)

ACCEPTABLE 
LOCATION

Fig. 4 

90cm

Fig. 5 

x

  Walls, partitions, barriers and lattice ceilings 

The JA-180S 

must not be installed closer than 0.5 m from any wall or 

partition

. A narrow room with a width of less than 1.2m requires the 

detector(s) to be placed at a distance of at least one third of the room’s width 
away. In the case of separating walls (partitions, warehouse objects) which do 
not reach the ceiling, the space is 

considered to be fully separated if the 

gap between the top of the separating wall and the ceiling does not 
exceed 0.3 m

. A free space of at least 0.5m is required under the detector. 

Irregularities in ceiling shape which do not exceed 5% of ceiling height are 
considered insignificant – the ceiling can be regarded as being even and limits 
from the table are applicable. 

However, any irregularity (including beams) 

exceeding 5% of the ceiling height is considered to be a wall with the 
consequences stated above

.

x

  Ventilation and air circulation 

The detectors must not be installed directly by a fresh air inlet

, e.g. 

air conditioning vents. In the case of air being supplied through a perforated 
ceiling, each detector must be placed so that no perforation hole occurs 
within 0.6m of the detector. 

x

  Avoid installing the detector in the following locations: 

 

Places with poor air circulation (niches, corners, apexes of A-shaped 
roofs). 

 

Places exposed to dust, cigarette smoke or steam. 

  Places with over-intense air circulation (close to ventilators, heat 

sources or air conditioning outlets). 

  Kitchens and other cooking places (because steam, smoke or 

oily fumes can reduce detector sensitivity). 

 

Beside lights (electrical interference can cause a false alarm) 

 

Areas with lots of small insects 

Caution: Most false alarms are due to detector 
misallocation 

See CEN/TS 54-14 standards for detailed installation guidelines. 

Installation

1.  Open the detector by turning the rear cover to the left and remove the 

battery 

2. 

Screw the rear cover

 onto the desired location  

3. 

Set the required function

 using the jumpers – see the table below 

4.  Please read the receiving device (control panel) installation manual before you 

connect the battery (remove the insulation tape) and set the control panel to 
enrollment mode  

5.  When the battery is connected, the detector sends a signal to connectto the 

system  

6.  After installing the detector, allow approx. 20 seconds for 

stabilisation. This period is indicated by the LED being continuously 
lit and is 

followed by an auto-test

. Successful performance of the 

auto-test is 

confirmed acoustically.

op

en

clo

se

LI

T

H

IU

M

 3,

6

V

 A

A

TEST

1

ON

INSTANT alarm mode 

3 OFF 

1

OFF 

FIRE alarm mode 

OFF 

Smoke (EN 14064)  
or heat (EN 54-5) 

ON Memory 

ON 

 

3  ON 

2

OFF Memory 

OFF 

4  OFF 

Only smoke (EN 14604) 
(heat indifferent) 

3 OFF 
4 ON 

Only heat (EN 54-5) 
(smoke indifferent) 

3 ON 

1

1

2

3

4

ON

OFF

4 ON 

Smoke and heat 
(both simultaneously) 

Testing the detector is automatically performed up to 10 secs 
after battery insertion. New settings are saved directly afterwards. 

J1:

 The 

FIRE / INST

 alarm mode jumper sets the reaction of the 

system. FIRE = alarm is triggered even if the system is disarmed while 
INST = alarm is triggered only in an armed system. The 

FIRE / INST

jumper only has an effect if the detector has a natural reaction 
assigned to its address in the Jablotron control panel.  It also has no 
effect when used with a JA-182N or JA-180N receiver.  