JA-116H BUS expander – 16 inputs

JA-116H BUS expander - 16 inputs

1 / 2

MLN55105

This product is a component of the 

JABLOTRON 100 system

. It is 

used for powering and connecting up to 16 detectors with contact 
outputs. It is possible to install the module straight into the JA-106K 
control panel. It should be installed by a trained technician with a valid 
certificate issued by an authorised distributor.

Installation

1. Put the module into the JA-106K box in the bottom right corner or 

to an installation box. 

2. Connect every single loop to the input terminals from 1 to 16 and 

the COM common terminals. Take power for the detectors from the 
+U and GND output terminals. The max. load current of connected 
devices is 100mA for each +U GND terminals.

Figure: Loop connection 

example

The mode of the 
connection is selectable 
for every input 
individually using F-Link 
sw in the module 

Internal settings.

x

Zones can be connected as NO (example: 1-COM), as NC 

(example: 2- COM), as a single balanced loop (example: 3-COM) 
or as a double balanced loop (example: 8-COM).
Activation by repeated pulses (e.g. a roller blind) is available for 
input terminals 1 to 8.

x

Balancing resistors for single and double balancing are 
selectable from these: 1k, 2k2, 3k3, 4k7, 5k6, 10k. The 
selection is common to all expander inputs. There are 32x 1k 
resistors in the module accessories. 

x

You are able to connect up to 5 devices (magnetic, PIR, or 
any other detectors) to one input terminal when you use a 
double balanced zone with 1k resistors

x

The maximum length of a wired loop is 100m.

Figure: Example of wiring more detectors to one input terminal when the 
loop is double balanced by 1k resistors. Connection of 2 magnetic 
contacts to the 4-COM input terminals. Connection of detectors with 
alarm and tamper contacts to the 5-COM input terminals.

3. When the module is mounted in an installation box, this box has to 

be equipped with a tamper contact. For external tamper contact 
connection, use any wired input terminal.

4. Connect the BUS cable. 

When connecting the module to the system 
BUS, always switch the power off.

5. Proceed according to the control panel installation manual. Basic 

procedure:

a.When the device is connected, the yellow LED (4) starts flashing 

repeatedly to indicate that the module has not been enrolled to the 
system.

b.Go to the F-Link software, select the required position in the 

Devices window and launch enrollment mode by clicking on the 

Enroll

button. 

Necessary condition:

After the selected position, 

the next 15 positions have to be free. 

c. Press the LEARN button (5) – the module is enrolled into the 16 

selected positions and the yellow LED goes off. Warning – the 
module is enrolled to sixteen (16) consecutive positions (each input 
is enrolled to one position). If some positions in those 15 are 
already occupied, they will be overwritten. When there are not 
enough positions at the end of the list of devices, only a limited 
number of inputs will be enrolled to fill in the rest of the positions. 

6. Close the installation box.

Figure: 
1 – BUS cable; 
2 – digital BUS terminals;  
3 – red LED indicator;
4 – yellow LED indicator; 
5 – LEARN (enroll) button;
6 – input terminals; 
7 – production code 

Note:

Enrolling the module 

to the system is possible by 
entering the production 
code (7) via F-link software 
or by a production code 
reader. All digits under the 
production code are 
required (1400-00-0000-
0001). 

Module settings

The Internal settings option (at any module position) in the 

Devices

window in the F - Link software opens a dialog window where you can 
set the following options for each output: (

*

factory settings):

LED activity indication:

Enabled

*

:

A short flash (3) indicates a 

status change on any input (activation and deactivation).

Balanced inputs:

The chosen value of balancing resistor R is 

common for all terminals of the module. You can choose between 1k*, 
2k2, 4k7, 5k6, or 10k. Valid for single and double balanced inputs. 

Inputs 1 - 8 and Inputs 9 - 16: 

Disabled

– no reaction (input is 

completely disabled), 

Enabled *

– input reacts to status change 

connected to the input terminal (NC is standby), 

Balanced

– contact  is 

connected in series with balancing resistor R (32 x 1k resistors are 
available in the accessories). Activation happens if the resistance rises 
or drops by more than 30% of the EOL resistor value, 

Rollerblind 

(inputs 1 - 8 only) reacts to short repeated pulses with sensitivity 
adjustable to two levels:  

Impulse 1 

= activation by 3 pulses up to max. 

2 minutes; 

Impulse 2

= activation by 5 pulses up to max. 2 minutes. 

Double balanced

– standby: connection to COM via the EOL resistor R 

(

r

20%), Activation: connection to COM via the EOL resistor 2R (

r

30%), Tamper: connection to COM via EOL resistor lower than R –30% 
or higher than 2R+30%.

Inverted input reaction:

(valid for Enabled or Balanced input). The 

default reaction is set to disconnection from COM (NC)*. By this you 
can set the opposite reaction to grounding (NO).

Pulse mode:

(valid for Enabled or Balanced input and inputs 1 to 8). 

The default is a status reaction, the input reacts to activation 
(disconnection from COM) and deactivation (connecting back to 
COM)*. If you tick this option, the input will only react to disconnection 
from COM (after 2s it returns to standby mode).

Delayed input reaction

: a time filter for increasing the immunity and 

to suppress false activations, 0.5 s* (options: 0.5s … 300 s). This tells 
you how long the input has to be activated to trigger an alarm in the 
control panel. It is possible to use the parameter with the input set as 
enabled (options from 0.1s), balanced and double balanced. 

Note: The expander faulty reports are recorded in the event memory 

of the control panel. The source of these events is the 1

st

input position, 

defined by enrolling.

The manufacturer only guarantees correct functioning 
of the module. However, it cannot guarantee the 
correct functioning of connected detectors. We 
therefore strongly recommend using Jablotron JA-100 
bus detectors.