JA-63ST (10S) wireless combined smoke and heat detector
The detector reports fire hazards and is triggered
by the presence of smoke or an abnormal increase
of temperature. Apart from sending reports to the
system it also triggers acoustic and optical
indication.
-
Open the detector cover
-
Attach the plastic base to the selected place
using screws
-
Enroll the detector to the system using the
A-Link software (see the
System extension
chapter)
-
Remove the isolation tape from the contacts of
one of the batteries
-
Attach the detector onto the base
Detector testing and maintenance
The detector should be tested at least once per month.
To test the detector press
the whole body of the detector against the base and wait until an LED indicator switches on.
The LED flashing signals switch over to the test mode. The LED flashes for the whole
duration of the test. When the test is complete, the LED switches off. The detector then
signals the result. If the detector beeps once, the test has been successful. If a failure is
discovered, the LED flashes and beeps three times. If the battery is low, there is just one
flash and no acoustic indication when the test is completed.
The complete functioning of the optical part of the detector can be tested with a test spray
(e.g. SD- TESTER). The heat sensor can be tested with heated air (e.g. with a hair dryer).
Warning: Never test the detector by starting a fire inside the premises
Tips and specifications
The detector cannot be fixed in the base until all three batteries are inserted
The smoke detector must be installed so that smoke easily drifts into the detector owing to natural
thermal circulation (avoid niches, corners, apexes of A-shaped roofs, etc.)
If the ceiling is divided by obstacles which obstruct the flow of air then each section must have its own
detector
It should not be installed close to ventilators, heat sources, air conditioning outlets and dusty places
It’s not recommended to install it near stoves, cookers and places with an occurrence of steam
A suitable place for installation is a ceiling above a staircase
In the case of an alarm, the siren can be silenced by pressing the detector’s body against its base.
Silence lasts for 10 minutes, if the detector still detects smoke or heat after this time has expired, the
indication will be renewed.
The siren may be completely disabled by inserting a jumper (included) on the pair of pins called SIR
If people in the premises smoke on a regular basis, Azor can be configured to react to a fire hazard
only when the system is set – see Settings. In this case, also disconnect the siren in the detector.
Don’t forget to air out the room before setting the system
Configuration terminals MEM, TEMP, SMOKE and INST must stay disconnected
Low battery indication
If the batteries are low, Azor will send a message with this information. The smoke
detector will also flash approximately every 30 seconds.