Page 19
Operation and Maintenance
ThermoCooler HP
DSTCH.191101.01.EN
Continuous product development may give rise to specification changes without notice.
7 Technical data
Size
100
150
190
240
300
360
400
480
600
740
850
980
Air flow min
(a)
m
3
/s 0.25
0.38
0.50
0.58
0.68
0.85
0.92
1.07
1.34
1.71
1.98
2.38
Air flow max
(a)
m
3
/s 0.95
1.61
2.12
2.48
2.91
3.64
3.93
4.61
5.75
7.34
8.47
9,95
Max cooling power
(b)
kW
13.2
21.3
27.1
29.1
40.1
48.3
51.0
65.1
81.7
99.5
113.3
129.1
No. of compressors units
1
1
1
1
1
1
1
1
2
2
2
2
Max operating
current
A
7.6
11
15
15
21
24
26
33
44
52
63
65
External fuse protec-
tion
(c)
A
10
16
20
20
25
32
32
40
50
63
80
80
Refrigerant R410a
kg
2.8
4.6
5.8
7.0
8.2
10.1
10.7
13.2
10.4 +
5.8
14.0 +
6.0
14.0 +
9.0
17.4 +
12.6
a) For units with dampers, ePM1-50% (F7) filter supply air,
ePM10-60% (
M5) filter extract air, SFPv values with NP rotor,
supply air temp 20°C and duct pressure 200 Pa (170+30 Pa). Max. air flow calculated with a minimum 10% spare capa-
city for fans.
b) With outdoor temp 26°C, 50% RH and extract air temp 22°C.
c) Regarding cooling/heating pump at 3×400V+N 50 Hz. Fuses with type C characteristics. The air handling unit is fused
separately and the fuse protection size varies depending on selection of fan variants.