IV Continuous product development may give rise to specification changes without notice.
2014-11-04
1 (2)
Product sheet
Operation and Maintenance
Flexomix MIE-EL
Electric air heater fitting
(code MIE-EL)
MIE-EL coil fitting is designed for electric air heater
(code ELEE). The fitting consists of assembly rails,
inspection doors and a housing front section for inte-
gration into the standard module (code EMM).
The electric air heater (code ELEE) is an electric heater
in a high-temperature design.
• The heating rods consist of stainless pipe elements
SS 2337 / AISI 321.
• The heater has double over-temperature guards
that cut the power if there is a risk of overheating.
One of the guards is reset manually.
• Protection IP43 in accordance with SS-EN 60529.
• Also available with integrated control equipment
(HS) for power control.
• There are up to five output variants per size avail-
able as standard. Other outputs may, however, be
supplied to specification.
Insert damping (dB)
Octave band
intermediate
frequency (Hz)
63
125
250
500
1000
2000
4000
8000
ELEE
1
1
1
1
1
1
1
1
Technical data, size 060
Configuration
Electrical data
Output
variant
Min. air
flow
(m³/s)
Total
output
(kW)
Rated
current (A)
2×400V~50Hz
Rated
current (A)
3×400V~50Hz
01
0.2
3.0
10
–
02
0.2
6.0
–
8.7
03
0.2
13.0
–
18.8
04
0.2
24.0
–
34.6
05
0.2
30.0
–
43.3
Power stage HT (without control system)
Output
variant
Output steps (kW)
1
2
3
4
01
3.0
–
–
–
02
6.0
–
–
–
03
13.0
–
–
–
04
24.0
–
–
–
05
2.0
4.0
8.0
16.0