background image

8

C O B R A

5 1 0 0 5 9 9   R e v .   D

6. TROUBLESHOOTING

NOTE – 

Only quali

fi

 ed service personnel are to perform troubleshooting 

tasks.

Operational Check:

1. Rub a small strip of plastic 

fi

 lm until a static charge is developed (cellophane 

works well).  The charge will be evident by the 

fi

 lm’s attraction to your hand.

2. Pass the 

fi

 lm in front of the gun while depressing the trigger.  Hold the 

fi

 lm to 

see if it is still attracted to your hand.

3. If the 

fi

 lm is no longer attracted to your hand, the static charge has been neutral-

ized and the gun is working properly.

Cable Retermination:

If the cable becomes damaged, it can be shortened to remove the damage and 
reterminated.

CAUTION – 

Electrical Shock Hazard – Always disconnect power supply 

before connecting or disconnecting static neutralizing equipment. Avoid 
touching static neutralizing point when power supply is energized.

1. Disconnect and remove damaged cable from the power supply.
2. Cut off damaged cable, remove 2” clear tubing and slide approximately 10” 

onto gun cable.

3. Strip 4½ ” from the black outer jacket.

NOTE – 

Use extreme caution not to damage or nick the white wire

insulation.

4. Strip the white wire insulation 1” and bend the conductor to form a double 

thickness ½” long.

5. Remove the spring loaded cable connectors (SLCC) from the damaged cable 

and install them onto the prepared cable.

6. Secure the cable to the power supply using a strain relief 

fi

 tting and install the 

SLCC’s into the power supply’s output terminals.

Содержание SIMCO ION COBRA

Страница 1: ...COBRA 5100599 Rev D COBRA Static Neutralizing Blow off Gun with G165 and G255 Power Supplies INSTALLATION AND OPERATING INSTRUCTIONS ...

Страница 2: ...COBRA 5100599 Rev D TABLE OF CONTENTS 1 INTRODUCTION 3 2 SAFETY 4 3 SPECIFICATIONS 5 4 INSTALLATION 6 5 OPERATION 7 6 TROUBLESHOOTING 8 7 MAINTENANCE 10 8 REPLACEMENT PARTS 11 9 WARRANTY 11 ...

Страница 3: ...ach power unit can energize one or two guns and features an on off switch with a power indicator light Receipt of equipment 1 Carefully remove the equipment from its carton 2 Inspect contents for damage that may have occurred during shipment If any damage has occurred the local carrier should be notified at once A report should be forwarded to Simco Ion 2257 North Penn Road Hatfield PA 19440 and 2...

Страница 4: ...rly grounded including the machine frame to which the equipment is mounted 4 Do not operate device in excess of specifications NOTE Do not insert objects into the intake or outlet of the gun CAUTION Electrical Shock Hazard Always disconnect power supply before connecting or disconnecting static neutralizing equipment Avoid touching static neutralizing point when power supply is energized CAUTION F...

Страница 5: ...l Type 302 Ionizing Point Compressed Air Supply Pressure 1 4 NPT Connection 100 PSIG Maximum Note Gun body includes OSHA pressure relief feature Air Consumption 9 SCFM at 30 PSIG 22 SCFM at 100 PSIG Ion Balance 100 V at 6 Noise Level 92 dB at 30 psig 2 from gun 101 dB at 30 psig 2 from gun Discharge Time 0 6 seconds at 6 30 psig 1000V to 100V 0 5 seconds at 6 100 psig 5000V to 500V Discharge Time ...

Страница 6: ...ow 4 The power supply is grounded when plugged into a 3 prong electrical outlet If a grounded outlet is not available connect a heavy copper wire from the ground terminal of the power supply to a well grounded electri cal conduit or water pipe The 230 volt power supply will require installation of an appropriate plug onto the end of the line cord The 230 volt connections are Black Line White Line ...

Страница 7: ...rmance first blow off the target surface with the gun held as close to the surface as required to remove dirt and dusts Then use a broad sweep ing motion with the gun 12 to 24 from the surface Be sure that the ionized air stream from the gun contacts all areas of the target surface to ensure thorough static neutralization The COBRA gun is supplied with an accessory nozzle that produces a fan shape...

Страница 8: ... damage and reterminated CAUTION Electrical Shock Hazard Always disconnect power supply before connecting or disconnecting static neutralizing equipment Avoid touching static neutralizing point when power supply is energized 1 Disconnect and remove damaged cable from the power supply 2 Cut off damaged cable remove 2 clear tubing and slide approximately 10 onto gun cable 3 Strip 4 from the black ou...

Страница 9: ...d either the gun or the power supply is defective To identify which is not working Deenergize the power supply Disconnect all static control devices from the power supply by unscrewing the knurled plugs and gently pulling out each high voltage cable Connect an insulated test wire to the power supply s ground stud Energize the power supply Slowly insert the free end of the test wire into one of the...

Страница 10: ...energize all power supplies before performing any maintenance tasks 2 Allow a gentle flow 5 10 psig of compressed air through the gun during maintenance 3 Use dry compressed air to remove loose particulate from the gun A soft brush with plastic bristles may be used as well 4 Press a soft pencil eraser onto the ionization point and gently twist to remove any buildup 5 Wipe ionization point with iso...

Страница 11: ...n tampered with misused improperly installed altered has received damage through abuse carelessness accident connected to improper line voltage or has been serviced anyone other than an authorized factory representative The warranty does not apply when Simco Ion parts and equipment have been energized by other than the appropriate Simco Ion power supply or generator or when a Simco Ion power suppl...

Страница 12: ...COBRA 5100599 Rev D Simco Ion 2257 North Penn Road Hatfield PA 19440 215 822 6401 800 203 3419 www simco ion com customerservice simco ion com 2011 Simco Ion Printed in the U S A ...

Отзывы: