This manual describes the GB50 Series Piston 
Actuators. Actuators of various piston diameters, 
strokes, and mounting arrangements are available.  
These piston actuators are typically equipped with a top 
mounted positioner and range (control) spring assembly.  
Other configurations are available, including on-off (full 
extend / retract) operation, failsafe operation, and 
different mounting or lever operation.  See sales 
literature for these standard offerings.  
 

UNPACKING ACTUATOR 

 
Check for accessory equipment packed with the 
actuator. The actuator nameplate will provide necessary 
data required for complete identification. Always refer to 
actuator model number when ordering spare parts, 
conversion parts or accessory equipment.  
 

INSTALLATION 
 

The piston actuator can be mounted in any position. In 
most configurations, a regulator and gauge for loading 
one side of the piston are mounted and piped. Air supply 
should be regulated and filtered.  
 
NOTE: A Conoflow Airpak (filter-regulator) can be 
integrally mounted to provide constant regulation and 
filtration of air supply to the actuator

.  

 
 
 
 
 

OPERATION 
 

Normal range of the actuator positioner for full stroke is 
3-15 PSI (21-103kPa) (Other ranges, including 3-9 PSI 
(21-62 kPa) and 9-15 PSI (62-103 kPa) are available). 
Connect the signal input to the connection marked 
“INST,” on the positioner. Then connect a supply of 
clean, filtered air to the supply connection port to supply 
both the positioner and the cushion loading device. The 
supply pressure required is a function of the cylinder 
diameter and the force required. Air supply up to 100 
PSI (690 kPa) can safely be used to insure a reserve of 
power and maximum speed. However, for economy of 
operation, use the lowest supply pressure with which 
satisfactory results can be obtained.  The positioner has 
been tested, and adjusted for operation with a supply 
pressure up to 100 PSI (690 kPa). 
 

ZERO ADJUSTMENT 
 

To check the zero adjustment (preset at factory), set the 
instrument output signal at the mid-point of its range (9 
Psi (62 kPa) on a 3-15 PSI (21-103 kPa) range), turn 
zero adjustment coupling and note the position of the 
actuator stem. Continue rotation of the zero adjustment 
coupling in the proper direction until the actuator stem is 
at the midpoint of stroke. Adjust the instrument output 
signal to low and high points in the range and check the 
stem position at both ends of the stroke.  
 
If stroke adjustment does not fall within specifications, 
refer to the positioner manual for further instructions. 
 

CUSHION LOADING REGULATOR 
 

Fixed cushion loading pressure has been arbitrarily set 
at approximately 20 PSI (138 kPa). This pressure may 
be adjusted by means of the cushion loading regulator 
when higher or lower return forces are required. The 
standard regulator supplied can provide settings up to 60 
Psi (414 kPa) and as low as 5 PSI (35 kPa).   

WARNING 

Conoflow’s products are designed and 
manufactured using materials and workmanship 
required to meet all applicable standards.  The use 
of these products should be confined to services 
specified and/or recommended in the Conoflow 
catalogs, instructions, or by Conoflow application 
engineers. 
 
To avoid personal injury or equipment damage 
resulting from misuse or misapplication of a 
product, it is necessary to select the proper 
materials of construction and pressure-
temperature ratings which are consistent with 
performance requirements.

 

Содержание Conoflow GB50 Series

Страница 1: ...input to the connection marked INST on the positioner Then connect a supply of clean filtered air to the supply connection port to supply both the positioner and the cushion loading device The supply...

Страница 2: ...positioner from the head plate GB50 Remove the set screws and lift out the cylinder head plate GB51 55 Remove the cover Spirolox type retaining ring and lift out the cylinder head plate Disconnect th...

Страница 3: ...or Positioner V GC34 Commandaire Positioner with Cushion Load Regulator F GC31 Commandaire Positioner with full reversal GH232T Reversing Relay and GFX04 Supply Filter G GC33 Commandaire Positioner wi...

Страница 4: ...TSIDE THE UNITED STATES CONTRARY TO THE REQUIREMENTS OF THE EAR FIGURE 1 GB50 SERIES ACTUATOR LABELED SECTION VIEW SHOWING CURRENT PISTON SEAL GB50 SIZE FIGURE 2 GB51 53 SERIES ACTUATOR LABELED SECTIO...

Страница 5: ...E CONTROLS OF THE EXPORT ADMINISTRATION REGULATIONS EAR THIS INFORMATION SHALL NOT BE PROVIDED TO NON US PERSONS OR TRANSFERRED BY ANY MEANS TO ANY LOCATION OUTSIDE THE UNITED STATES CONTRARY TO THE R...

Страница 6: ...D E F G H J K L M STROKE GB50XC2 3 3 1 2 6 1 8 3 3 4 13 15 16 1 2 20 5 16 11 32 2 3 4 5 1 4 2 GB50XC5 9 1 8 6 3 4 19 15 16 5 GB50XC8 12 1 8 9 3 4 25 15 16 8 GB50XCA2 6 1 8 10 3 16 5 16 18 1 2 2 3 4 2...

Страница 7: ...1CX4 8 1 16 6 18 5 8 4 GB51XCA3 7 1 16 11 5 8 3 8 16 1 2 3 1 4 3 GB51XCA4 8 1 16 12 5 8 4 GB51XW3 5 7 1 2 5 12 1 2 3 8 13 32 2 3 4 3 GB51XW4 8 1 2 6 14 1 2 4 GB51XWA3 7 1 2 3 8 16 1 2 3 1 4 3 GB51XWA4...

Страница 8: ...8 4 10 3 8 1 2 17 32 3 3 4 9 1 2 1 1 2 GB53XW4 9 17 32 6 15 7 32 11 3 4 4 GB53XW6 11 25 32 8 19 25 32 11 3 4 6 GB53XW8 13 25 32 10 23 25 32 14 1 2 8 GB53XW10 15 25 32 12 27 25 32 14 1 2 10 GB53XWA112...

Отзывы: