24
How to Install the ISONAS PureIP Reader-controller
2.2.8
: EDK LED STATUS INDEX
The EDK has two status LEDs
Power LED:
Located on the side towards the Pure IP Reader-Controller’s pigtail.
A Red LED indicates 12VDC power is being supplied to the EDK.
Communication Status LED:
Located on the side towards the Lock wiring.
LED status meaning are described in the table below.
Pure IP
Reader-
Controller
Locked
Pure IP
Reader-
Controller
Unlocked
Lock State when
Pure IP Reader-
Controller is
unlocked
Description or Item to Check
Off
Green
Normal Operation
Flash
Amber
Flash
Amber
No Operation
Yellow wire may be disconnected
Off
Flash
Amber
No Operation
White wire may be disconnected
Off
Flash
Amber
No Operation
Invalid encryption key received from Pure IP
Reader-Controller
Off
Off
No Operation
If PowerCycle of Pure IP Reader-Controller
allows for one or more lock operations,and
then the lock stops operating, then the
BackEMF diode may not be installed correctly.