MENU 7 - OUTPUTS
Function choice corresponding to digital Output 1. The functions are listed in the table below.
Function choice corresponding to digital Output 2. The functions are listed in the table below.
This function sets the current output 1 and 2. This function is optional and will not appear unless the option has been
requested. There are three fields to modify for this function:
Scale zero: 4 or 0mA
Full scale: 20 or 22mA
Field: + = positive, - = negative, blank = both, -0+ = central zero scale
The values corresponding to the scale points are shown in the following chart:
(POS. 7.1) OUTput 1 Function
[Out1=XXXXXX]
AL3
[OUT1F]
(POS. 7.2) OUTput 2 Function
[Out2=XXXXXX]
AL3
[OUT2F]
(POS. 7.3-4) Analog Output 1/2 ConFiguration
[Out mA1/2=X_XX XXX]
AL3
[AO1CF] [AO2CF]
FUNCTIONS FOR OUTPUTS 1 AND 2
OFF:
DISABLE
MAX AL. +
: MAX DIRECT FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
MIN AL. +:
MIN DIRECT FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
M
AX AL.-:
MAX INVERSE FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
MIN AL.-
: MIN INVERSE FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
MAX/MIN
-: MAX/MIN INVERSE FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
MAX/MIN+/
-: MAX/MIN DIRECT FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
P.EMPTY:
EMPTY PIPE ALLARM OUTPUT (ENERGIZED = AL. OFF)
AL.SYSTEM:
SUM OF ALL ALARMS ”energized interrupted ” AND ”error input signal ”
OVERFLOW:
OUT OF RANGE ALLARM OUTPUT (ENERGIZED = FLOWRATE OK)
ALL ALARMS:
SUM OF ALL ALARMS POSSIBLE
MANUAL:
OUTPUT MAY TAKE A STATE EMPLOYEE FROM AN EXTERNAL CONTROL (MCP,MODBUS,ecc)
FLOW RATE SIGN.:
FLOW DIRECTION (ENERGIZED WHEN FLOW IS NEGATIVE)
SCALE:
INDICATION SCALE
FREQ.+:
FREQUENCY POSITIVE FLOWRATE
FREQ.-:
FREQUENCY NEGATIVE FLOWRATE
FREQ.+/-:
FREQUENCY POSITIVE/NEGATIVE FLOWRATE
:
PULSE POSITIVE FLOW RATE
PULSES.-:
PULSE NEGATIVE FLOW RATE
/-:
PULSE NEGATIVE/POSITIVE FLOW RAT
E