SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 22 of 25
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
40096
95
0x5F
CCounter 6 MSR
Read/write
40097
96
0x60
CCounter 7 LSR
Read/write
32-bit value of
captured counter 7
40098
97
0x61
CCounter 7 MSR
Read/write
40099
98
0x62
CCounter 8 LSR
Read/write
32-bit value of
captured counter 8
40100
99
0x63
CCounter 8 MSR
Read/write
40117
116
0x74
Counter Config 1
Read/write
Counter Configuration
+1 – time
measurement (if 0
counting impulses)
+2 – autocatch counter
every 1 sec
+4 – catch value when
input low
+8 – reset counter
after catch
+16 – reset counter if
input low
+32 – encoder (only for
counter 1 and 3)
40118
117
0x75
Counter Config 2
Read/write
40119
118
0x76
Counter Config 3
Read/write
40120
119
0x77
Counter Config 4
Read/write
40121
120
0x78
Counter Config 5
Read/write
40122
121
0x79
Counter Config 6
Read/write
40123
122
0x7A
Counter Config 7
Read/write
40124
123
0x7B
Counter Config 8
Read/write
40133
132
0x84
Catch
Read/write
Catch counter
40134
133
0x85
Status
Read/write
Captured counter
Table 9. Registered access
Bit Access
Modbus
Address
Dec Address
Hex
Address
Register Name
Access
Description
193
192
0x0C0
Default State of
Output 1
Read/write
Default state of
output 1
194
193
0x0C1
Default State of
Output 2
Read/write
Default state of
output 2
195
194
0x0C2
Default State of
Output 3
Read/write
Default state of
output 3
196
195
0x0C3
Default State of
Output 4
Read/write
Default state of
output 4
197
196
0x0C4
Default State of
Output 5
Read/write
Default state of
output 5