SfAR-1M-4DI User Manual

www.ismacontrolli.com

DMP269en | 3rd Issue rev. 1 | 05/2022

page 7 of 16

4  Communication

4.1  Grounding and Shielding

In most cases, I/O modules will be installed in an enclosure along with the other devices, 

which  generate  electromagnetic  radiation.  Relays,  contactors,  transformers,  motor 

invertors,  etc.,  are  examples  of  such  devices.  Radiation  can  induce  electrical  noise  into 

both power and signal lines, as well as direct radiation into the module. Whether or not 

the SfAR modules are immune to such effects, the interferences must be suppressed at 

their  source  if  possible  to  ensure  the  proper  functioning  of  the  entire  system. 

Appropriate  grounding,  shielding  and  other  protective  steps  should  be  taken  at  the 

installation stage to prevent these effects. It is recommended to at least follow the rules 

below:

line  power  cables  must  be  routed  with  spatial  separation  from  signal  and  data 

transmission cables;

analog and digital signal cables should also be separated;

it is recommended to use shielded cables for analog signals, cable shields should not 

be interrupted by intermediate terminals;

the shielding should be earthed directly after the cable enters the cabinet.

It  is  recommended  to  install  interference  suppressors  when  switching  inductive  loads 

(e.g., coils of contactors, relays, solenoid valves). RC snubbers or varistors are suitable for 

AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must 

be connected as close to the coil as possible.

4.2  Network Termination

Transmission  line  effects  often  present  problems  for  data  communication  networks. 

These problems include reflections and signal attenuation. To eliminate the presence of 

reflections of signal from the end of the cable, the cable must be terminated at both ends 

with a resistor across the line adequate to its characteristic impedance. Both ends must 

be  terminated  since  the  propagation  is  bidirectional.  In  case  of  an  RS485  twisted  pair 

cable, this termination is typically 120 

Ω.

4.3  Types of Modbus Functions

There are 4 types of Modbus functions supported by the SfAR modules.

Type

Beginning Address

Variable

Access

Modbus Command

1

00001

Digital Outputs

Bit 

Read/write

1, 5, 15

2

10001

Digital Inputs

Bit 

Read

2

3

30001

Input Registers

Registered 

Read

3

Содержание SfAR-1M-4DI

Страница 1: ...www ismacontrolli com DMP269en 3rd Issue rev 1 05 2022 SfAR 1M 4DI User Manual Expansion Module 4 Digital Inputs ...

Страница 2: ...cation 7 4 1 Grounding and Shielding 7 4 2 Network Termination 7 4 3 Types of Modbus Functions 7 4 4 Communication Settings 8 4 4 1 Default Settings 8 4 5 Configuration Registers 8 5 Indicators 10 6 Connections 11 6 1 Block Diagram 11 6 2 Power Supply Connection 11 6 2 1 DC Power Connection 11 6 2 2 AC Power Connection 12 6 3 Communication Bus Connection 12 6 4 Connection of Digital Inputs 12 7 Mo...

Страница 3: ...f the product without incurring any liability for the purposes of commercial law This information does not discharge you from the liability of your own judgement and verification We reserve the right to change product specifications without notice Please read the instructions carefully and follow the recommendations concluded therein 1 1 Revision History Rev Date Description 3 1 25 May 2022 Rebran...

Страница 4: ...enomena like surges and bursts to devices They also isolate products from inductive phenomena from other transformers and loads Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges Avoid powering the product and its controlled monitored devices especially high power and inductive loads from a single power source Power...

Страница 5: ...rovides fast processing and quick communication The baud rate is configurable from 2400 to 115200 The module is designed for mounting on a DIN rail in accordance with DIN EN 5002 The module is equipped with a set of LEDs to indicate the status of inputs and outputs which is useful for diagnostic purposes and helping to find errors Module configuration is done via USB by using a dedicated computer ...

Страница 6: ...ower supply 3 pin Communication 3 pin Inputs 2 x 3 pin Configuration mini USB Size Height 90 mm Length 56 4 mm Width 17 5 mm Interface RS485 Up to 128 devices Table 2 Technical specification 3 3 Dimensions The appearance and dimensions of the module are shown below The module is mounted directly to the rail in the DIN industry standard Figure 1 Dimensions ...

Страница 7: ...signals cable shields should not be interrupted by intermediate terminals the shielding should be earthed directly after the cable enters the cabinet It is recommended to install interference suppressors when switching inductive loads e g coils of contactors relays solenoid valves RC snubbers or varistors are suitable for AC voltage and freewheeling diodes for DC voltage loads The suppressing elem...

Страница 8: ...in the 16 bit registers The access to registers is via Modbus RTU or Modbus ASCII 4 4 1 Default Settings Parameter Name Value Address 1 Baud rate 19200 Parity No Data bits 8 Stop bits 1 Reply delay ms 0 Modbus type RTU Table 4 Default settings 4 5 Configuration Registers Modbus Address Decimal Address Hex Address Name Values 40003 2 0x02 Baud Rate 0 2400 1 4800 2 9600 3 19200 4 38400 5 57600 6 115...

Страница 9: ...n 3rd Issue rev 1 05 2022 page 9 of 16 Modbus Address Decimal Address Hex Address Name Values 40004 3 0x03 Data Bits 7 7 data bits 8 8 data bits 40006 5 0x05 Response Delay Time in ms 40007 6 0x06 Modbus Mode 0 RTU 1 ASCII Table 5 Configuration registers ...

Страница 10: ...6 5 Indicators Figure 2 Indicators Indicator Description ON The LED indicates that the module is correctly powered TX The LED lights up when the unit received the correct packet and sends the answer DI1 2 3 4 The LED indicates that on the input is high state Table 6 Description of indicators ...

Страница 11: ...er Manual www ismacontrolli com DMP269en 3rd Issue rev 1 05 2022 page 11 of 16 6 Connections 6 1 Block Diagram Figure 3 Block diagram 6 2 Power Supply Connection 6 2 1 DC Power Connection Figure 4 DC power connection ...

Страница 12: ...m DMP269en 3rd Issue rev 1 05 2022 page 12 of 16 6 2 2 AC Power Connection Figure 5 AC power connection 6 3 Communication Bus Connection Figure 6 Communication bus connection 6 4 Connection of Digital Inputs Figure 7 Connection of digital inputs ...

Страница 13: ...ode ASCII or RTU 40009 8 0x08 Watchdog Read write Watchdog 40033 32 0x20 Received Packets LSR Least Significant Register Read write No of received packets 40034 33 0x21 Received Packets MSR Most Significant Register Read write 40035 34 0x22 Incorrect Packets LSR Read write No of received packets with error 40036 35 0x23 Incorrect Packets MSR Read write 40037 36 0x24 Sent Packets LSR Read write No ...

Страница 14: ...0067 66 0x42 CCounter 4 LSR Read write 32 bit value of captured counter 4 40068 67 0x43 CCounter 4 MSR Read write 40069 68 0x44 Counter Config 1 Read write Counter configuration 1 time measurement if 0 counting impulses 2 autocatch counter every 1 sec 4 catch value when input low 8 reset counter after catch 16 reset counter if input low 32 encoder 40070 69 0x45 Counter Config 2 Read write 40071 70...

Страница 15: ...ounter 1 1154 1153 0x481 Capture 2 Read write Capture counter 2 1155 1154 0x482 Capture 3 Read write Capture counter 3 1156 1155 0x483 Capture 4 Read write Capture counter 4 1169 1168 0x490 Captured 1 Read write Captured value of counter 1 1170 1169 0x491 Captured 2 Read write Captured value of counter 2 1171 1170 0x492 Captured 3 Read write Captured value of counter 3 1172 1171 0x493 Captured 4 R...

Страница 16: ...s network as well as to read and write the current value of other registers of the module It is a convenient way to test the system as well as to observe real time changes in the registers Communication with the module is via the USB cable The module does not require any drivers Figure 8 PC connection The SfAR Configurator is a universal software where it is possible to configure all available mod...

Отзывы: