MVC503R-MB Configuration Tool
–
Product Manual
12
Figure
13. Actuator configuration box
•
Action:
it allows to select direct or reverse action
•
Calibration:
it allows to start the stroke calibration of the actuator
P
ress the “READ” button to read the current status, the select from the drop
-
down menu the label “Learning” and press the button “WRITE”. At the end of the
calibration the status Running will be shown again by pressing the “READ”
button.
•
Failsafe:
it allows to select the emergency return position of the actuator
selectable between “
Up
” or “
Down
”.
•
Stroke:
it allows to set the fixed stroke mode or the automatic calibration mode;
If the fixed stroke mode is selected, the stroke value has to be set in the
Valve Stroke textbox and it’s necessary to press the “
Write Device
” button
in the top menu to save it.
Make sure that the other 2 parameters in the section mentioned above are the
current ones otherwise the actuator settings will be overwritten.
•
Speed:
selectable between 5 sec/mm (default) or 3 sec/mm.
Once the configuration parameters described above have been selected, press the
“
Write Device
” button and verify with
the “
Read Device
” button that the parameters
have been correctly set.
In order to make the parameters changes active, it’s necessary to reset the
actuator through the “RESET”.
3.5
“
Valve Configurati
on”
Box
In this box it is possible to set the following configuration parameters of the valve: