DMP116it | 1
st
Issue rev. a | 03/2022
pag.
MVC503R-MB Configuration Tool
–
Product Manual
11
After press the
CONNECT
button verify if
Modbus Status
is
OK
.
The parameters set in the Modbus Configuration box are requested only the first time
the software and the Serial converter are used.
3.3
“Modbus Configuration” Box
In this box it is possible to set the modbus configuration parameters.
Figure
12. Actuator Modbus configuration
•
Baud Rate
(selectable between 9600 and 19200).
•
Parity Bit
(selectable between none, odd and even)
•
Stop Bit
(selectable 1 or 2)
The default communication parameters are: 9600, No parity and 2 stop bits.
To write the configuration inside the actuator press the “
Write Device
”
button on the
top menu.
3.4
“Ac
tuator Configuration
”
Box
In this box it is possible to set the following configuration parameters of the actuator: