Installation - Overview
UNIT INSTALLED THROUGH FRONT OF
CLOSET (RECOMMENDED)
UNIT INSTALLED THROUGH
SIDE OF CLOSET
Top View
Top View
ARCHITECTURAL LOUVER
ARCHITECTURAL LOUVER
RTS
CONNECTION
~2 1/4”
3” MIN.
DOOR/ACCESS
PANEL
~1”
3” MIN.
10”
DUCT
ELECTRICAL
CONNECTION
19-7/8”
4” MIN.
UNIT FRONT
~2 1/4”
3” MIN.
3” MIN.
7” RECOMMENDED,
5” MIN.
DOOR/ACCESS
PANEL
ELECTRICAL
CONNECTION
RTS
CONNECTION
~1”
19-7/8”
PLENUM CUTOUT
32-1/4”H x 20-1/8”W
OUTSIDE WALL
WALL PLENUM - EXTEND
1/4” FOR CAULKING
EXTERIOR/OUTSIDE
EXTERNAL
DRAIN LINE
Side View
INSIDE WALL
8” MIN. FOR
DRAIN ACCESS
•
4” MIN. FROM FRONT OF CHASSIS - UNIT
INSTALLED THROUGH FRONT OF CLOSET
•
•
3” MIN. FROM TWO SIDES OF CLOSET
2-INCH (MIN.)
10-INCH (MAX.)
FOR OPTIMAL SERVICEABILITY AND UNIT ACCESSIBILITY,
THE FOLLOWING MINIMUM ACCESS OPENING SIZE IS
REQUIRED:
OPENING WIDTH = 28” MIN.
OPENING HEIGHT = 48” MIN.
Refer to “Interior Return Air Grille” installation instructions for standard factory access door
cut out (rough opening) dimensions.
10”
DUCT
UNIT FRONT
5” MIN. (7” RECOMMENDED) FROM
FRONT OF CHASSIS - UNIT INSTALLED
THROUGH SIDE OF CLOSET
FILTER
BRACKET
WALL PLENUM
BOTTOM OF CHASSIS
APPROX. 2.5” ABOVE
BOTTOM OF PLENUM
OUTSIDE WALL
FIELD SUPPLIED
OUTER FLASHING
Figure 2
Dimensional Drawings (Chassis)