ise smart connect KNX Hue
Commissioning
Order No. 1-0002-003
Product Manual Page 42 (60)
6.4
Accelerate transfer: Select transfer path KNX-TP or IP
Programming (transfer from the ETS to the device) occurs in the programming environment of the ETS.
An additional KNX data interface is not required for transfer (bus connection via bus connection termi-
nal). The ETS can reach the device from both the IP side and the KNX-TP side.
Due to considerably shorter transfer times, we recommend downloading from the device's IP page.
Figure 7:
The
Use direct KNX-IP connection if available
setting
accelerates the transfer from the ETS to the device.
For transfer of the ETS over the IP side, set the setting
Use direct KNX IP connection if available
on the ETS start page,
Settings
tab
Communication
entry
.
6.5
Programming the physical address of the device
Ensure that the device and bus voltage are switched on.
Ensure that the programming LED (4) is not illuminated.
Press programming button
(1) briefly − Programming LED (4) lights up red.
Program physical address using the ETS.
After a successful programming procedure,
LED (4) will go out.
The ETS shows the completed transfer with a green marking under
History
in the sidebar (nor-
mally at the right-hand window edge).
The ETS sets the commissioning tick on the device for "Adr" and "Cfg".
You can now note down the physical address on the device.