5.4.4
Pumps and valves
In this section you can see actual status of filtration pump, dosing pumps, and heating and make up water
valve. Active backwash process is shown in this section as well.
5.4.5
Runtimes
In this section you can find runtimes of each technological part based on real usage. These are total
runtimes.
5.4.6
Make up water
If maximal make up time is reached, alarm will be raised. Make up water valve will be blocked until reset
alert button is pressed. Perform a check if there is not a water leakage from the pool before hitting the
reset alert button.
5.4.7
Buffer tank
In this section you can find important information about buffer tank status and its protections.
H1- H4 indicate the current water level, H1 is on the top of the tank, and H4 is on the bottom.
Dry run protection: Protect filtration pump from running dry. If water is bellow H4, alert is
activated, filtration pump is blocked and make up water valve is opened to fill in water into the
buffer tank.
Forced pumping: Forced start of filtration pump for pumping water from buffer tank to swimming
pool. If water is above H1, alert is activated, filtration pump is started and make up water valve is
blocked.
Make up water: Automatic make up water valve is open.
Max. make up time: If maximal make up time is reached, alarm will be raised. Make up water valve
will be blocked until reset alert button is pressed. Perform check if there is not a water leakage or
contact a professional.
5.4.8
Sensors
In this section you can see the status of connected temperature and water quality measurement sensors.
If there is a problem with connection to sensor or a sensor malfunction, an alert will be raised.
5.4.9
Service intervals counter
Service interval counters are used to show remaining time until configured service interval will be reached,
individually for each of the technology parts.