Sensor Wiring
66
Modline 5
Wiring, grounding and shielding instructions are in the sections that follow.
Figure 57: Dimensions TSP
4.5
Sensor Interconnecting Cable Preparation
4.5.1
Cable Preparation
It is very important that the cable shield be properly prepared and installed. If the Terminal Strip Plate
is used, the shielding must be clamped to the ground shield clamps on the plate.
All cables must be properly dressed for shield grounding. Twisted pair wires must remain twisted and
kept as short as possible. The IRCON Sensor cable is supplied with the connector attached on one end.
The opposite wiring end is prepared and supplied as per the following procedure. If the cable is
shortened, the preparation procedure must be followed. User supplied cables require similar
preparation.
A. Strip off 10 in. (254 mm) of the outer jacket.
B. Partially cut back the outer braided shield. Leave 1 inch (26 mm) of shield exposed to attach a
strain relief or connection to a Terminal Strip Plate shield clamp.
C. Keeping wire pairs twisted, cut wires to lengths shown in the following table. Strip all wire pairs
ends 3/8 inch (10 mm) and tin with solder.
2.32 “(58.9mm)
5.03 “
(127.8 mm)