ipf electronic YT353120 Скачать руководство пользователя страница 1

YT353120

 

temperature monitor  

MANUAL • Subject to alteration! Version: 

June 2017

 

ipf electronic gmbh • Rosmarter Allee 14 • 58762 Altena 

 Tel +49 2351 9365-0 • Fax +49 2351 9365-19 

 [email protected] • www.ipf-electronic.com 

1

Содержание YT353120

Страница 1: ...temperature monitor MANUAL Subject to alteration Version June 2017 ipf electronic gmbh Rosmarter Allee 14 58762 Altena Tel 49 2351 9365 0 Fax 49 2351 9365 19 info ipf electronic com www ipf electroni...

Страница 2: ...oint page 10 window function with hysteresis page 10 operating modes page 11 programming page 12 list of parameters page 12 mounting and electrical connection page 15 connection of the PT100 sensors p...

Страница 3: ...cal data can lead to personal injury and or damage to property In all applications check compliance of the product materials Never use these devices in applications where the safety of a per son depen...

Страница 4: ...on of menu and parameters setting and saving of parameters Enter Set Enter Set 5 arrow key up setting the parameter values increasing the value fast keep the button pressed 6 arrow key down setting th...

Страница 5: ...u the indication will be shown on the display program button Enter Set symbol Enter Set Enter Set Selection of menus and submenus as well as confirming and saving of parameter values Short pressing in...

Страница 6: ...ock If the device is in the RUN Mode and you press the arrow keys at the same time for at least 5 seconds the keyboard lock will be activated The display shows sLOC blinking 3 times Now the adjusted s...

Страница 7: ...2 level MANUAL Subject to alteration Version June 2017 ipf electronic gmbh Rosmarter Allee 14 58762 Altena Tel 49 2351 9365 0 Fax 49 2351 9365 19 info ipf electronic com www ipf electronic com 7...

Страница 8: ...tween the switching outputs SP 1 and rSP 1 is 1 of the temperature range stated by the system The smallest adjustable hysteresis is 1 of the temperature range stated by the system All examples are eff...

Страница 9: ...ameters SP 1 50 0 C HYS 1 30 0 C An increasing temperature up to SP 1 e g 50 C switches the output according to the ad justed switching function no or nc This state remains also for higher temperature...

Страница 10: ...s rP 1 will remain the same windowfunction with hysteresis programmed parameters SP 1 50 0 C HYS 1 30 0 C If the temperature hits the adjusted window between SP 1 HYS 1 and SP 1 50 C the output switch...

Страница 11: ...e adjusted value the display blinks three times The unit now operates with the new adjusted value Returning to the RUN Mode Press the ESC button Enhanced menu programmimg mode Setting of the parameter...

Страница 12: ...e with the arrow keys Confirm the setted value with the Enter Set button 1X rP1 HYS1 Press the Enter Set button The current value for the release point S1 respectively the hysteresis will be displayed...

Страница 13: ...if in Ou 1 a switching function is set off delay timer function S1 Ou 2 Configuration Output 2 4 switching functions the error signal or 4 analog functions SP HY switch point hysteresis SP rP switch p...

Страница 14: ...a switching function is set on delay timer function S2 dr 2 ds 2 is active if in Ou 2 a switching function is set off delay timer function S2 HI saving the max temperature value of the system The hig...

Страница 15: ...no AY000060 After mounting the sensor mechanically the control panel can be rotated by 350 to align it for the machine operator The unit must be connected by a suitably qualified electrician The natio...

Страница 16: ...K030F25 with the temperature monitor For PT100 sensors with a fixed cable use a M12 connector e g VK003028 Depending on the version the connection pins must be bridged as you see below 2 wire 3 wire 4...

Страница 17: ...nal check wiring check load ERR sensor defect internal error S1 and S2 are switched off analog output error signal contact manufacturer AO If current output is selected analog output open If voltage o...

Страница 18: ...4mA adjustable start and end point burden max RL W Ub 8V 20mA error recognition analog output in case of line break current or short circuit voltage from 1V rise time 5msec 10 90 of PN damping 0 to 20...

Страница 19: ...y optical interface connection USB software AD000011 accessory mounting clip M12 socket Revised version 01 02 2010 internal software 4 13 cycle counter for SP1 Revised version 10 02 2016 analog output...