Quick Guide
Neutron4-B Remote Pulse Collector
Copyright 2017 - ionSign
www.ionsign.fi
13.2.2019
– v1.2
For example JAMAK 2x(2+1)x0,5mm2
instrumentation
cable
can
be
used
between the meter and Neutron4-B. The
relay output of a single meter is connected
to Neutron4-B as shown above.
Introducing Neutron4-B:
1.
Insert SIM card to its slot, PIN query
disabled.
2.
Connect the measuring device(s) and
antenna to the device.
3.
Insert the battery or remove the factory
installed battery cover. The red led
lights up for 10 seconds.
4.
Enter the installation mode by pressing
the button inside the device. The device
wakes up for five minutes to receive
SMS messages. The red GSM led
blinks twice at a time when GSM net-
work search is active, and once when a
GSM connection is established.
5.
Send the SETTINGS command to the
device as an SMS. When the command
is received, the yellow led starts blinking
and the device starts to establish a
server connection. The yellow led re-
mains lit when the device is in opera-
tion.
When installation mode times out, all leds are switched off. This is normal.
SETTINGS 101 services.ionsign.fi 80 internet 4 1 /cloud/input/ 0
*
Setting
“0” for servers that only support hourly data. Ignoring parameter sets 60 minute cycle.
The above example command sets
device 101 to start collecting hourly
pulse data and send it to server ser-
vices.ionsign.fi, path /cloud/input/
and port 80, using internet as APN.
Device 101 has 4 inputs and data is
sent one minute after 24 readings
have been collected. In this case, with
hourly data, at 00:01.
Red
GSM led
Antenna
SIM card
Battery
cover
Button
Pulse
connectors
Green, yellow
and red leds
Device
ID
Attached
meters
Server
name
Server
port
Server
path
Transmission
delay
Operator APN
address
Optional - Measurement cycle:
15, 30 or 60 (min) - 0=60min*