background image

 

 

Quick Guide 

Neutron12-3G Remote Pulse Collector 

 

 

 

 

Copyright 2017 - ionSign 

www.ionsign.fi 

14.3.2018 

– v1.7 

For 

example 

JAMAK 

2x(2+1)x0,5mm2 

instrumentation  cable  can  be  used  between 
the  meter  and  Neutron12-3G.  The  open 
collector  or  relay  output  of  a  single  meter  is 
connected to Neutron12-3G as shown above. 

Introducing Neutron12-3G: 

1. 

Insert SIM card to its slot on top of the de-
vice, PIN query disabled. 

2. 

Connect  the  power  supply,  meter(s)  and 
antenna to the device as in the enclosed 
diagram. Connect to the mains. 

3. 

Within 15 sec the 2G/3G led starts to dou-
ble  blink to indicate the  device  is looking 
for a GSM network. When connected, the 
2G/3G led only blinks once in intervals. 

4. 

A lit Signal led indicates a good GSM sig-
nal. If it blinks or remains off, try to find a 
better  place  for  the  antenna,  within  5 
minutes of power up. 

5. 

Send the 

SETTINGS

 command to the de-

vice as an SMS. A lit Init led indicates an 
established  server  connection.  If  the  Init 
led  remains  blinking,  the  command  was 
received, but server hasn

’t responded. 

When in operation, the PWR led toggles between ON/OFF with every pulse received. 

 

 

SETTINGS 101 services.ionsign.fi 80 internet 12 1 /cloud/input/ 

 
 
 
 

 

The above example command 
sets  device  101  to  start  col-
lecting  hourly  pulse  data  and 
send it to server services.ion-
sign.fi
,  path  /cloud/input/ 
and port 80, using internet as 
APN.  Device  101  has  12  in-
puts and data is sent one mi-
nute
 after midnight, at 00:01.

 

Device 

ID 

Attached 

meters 

Server 

name 

Server 

port 

Server 

path 

Transmission 

delay 

Operator APN 

address 