Quick Guide
Neutron12-3G Remote Pulse Collector
Copyright 2017 - ionSign
www.ionsign.fi
14.3.2018
– v1.7
For
example
JAMAK
2x(2+1)x0,5mm2
instrumentation cable can be used between
the meter and Neutron12-3G. The open
collector or relay output of a single meter is
connected to Neutron12-3G as shown above.
Introducing Neutron12-3G:
1.
Insert SIM card to its slot on top of the de-
vice, PIN query disabled.
2.
Connect the power supply, meter(s) and
antenna to the device as in the enclosed
diagram. Connect to the mains.
3.
Within 15 sec the 2G/3G led starts to dou-
ble blink to indicate the device is looking
for a GSM network. When connected, the
2G/3G led only blinks once in intervals.
4.
A lit Signal led indicates a good GSM sig-
nal. If it blinks or remains off, try to find a
better place for the antenna, within 5
minutes of power up.
5.
Send the
SETTINGS
command to the de-
vice as an SMS. A lit Init led indicates an
established server connection. If the Init
led remains blinking, the command was
received, but server hasn
’t responded.
When in operation, the PWR led toggles between ON/OFF with every pulse received.
SETTINGS 101 services.ionsign.fi 80 internet 12 1 /cloud/input/
The above example command
sets device 101 to start col-
lecting hourly pulse data and
send it to server services.ion-
sign.fi, path /cloud/input/
and port 80, using internet as
APN. Device 101 has 12 in-
puts and data is sent one mi-
nute after midnight, at 00:01.
Device
ID
Attached
meters
Server
name
Server
port
Server
path
Transmission
delay
Operator APN