Commissioning the GMU101: 

1. 

Insert the SIM card to its slot. Disable PIN 
query with a mobile phone, if enabled. 

2. 

Connect  antenna,  power  supply  and  nec-
essary Modbus device(s). 

3. 

When  powered  up  PWR  led  turns  ON, 
STA  led  flashes  once  and  then  STA  and 
STB leds flashes once simultaneously. 

4. 

The  GSM  led  blinks  twice  when  a  2G/3G 
network  is  being  looked  for.  GSM  blinks 
once when a network is available. 

5. 

Send  the  Settings

 

command  SMS  to  the 

SIM  card

’s  subscriber  number.  STA  led 

indicates 

that 

server 

connection 

is 

established. 

6. 

Modbus  master  reading  is  configured  on 
the server application (e.g. ionSign Cloud) 

7. 

Data collection and transfer has started. 

 

 

The  example  command  sets  device  121  to  collect  and  transfer  data  with  two-minute 
intervals  (120s)  to  server  services.ionsign.fi,  path  /cloud/input/  and  port  80,  using 
internet as APN. The device specific PIN code 1234 precedes the actual command. 

Always establish your specific SETTINGS parameters from your reseller. 

Operator 

APN is usually found in their web site: Search for “[your operator] APN settings”. 

  The device only accepts messages with a correct PIN. Required for all commands. 

  Server  Addresses  are  accepted  in  either 

IP  or  DNS  format.  Protocol  may  be 
appended to the address. 

  The device replies to all SMS commands, 

e.g. to SETTINGS: ”Settings saved”. 

  To 

all 

commands 

given 

without 

parameters,  the  reply  SMS  states  the 
current 

status 

or 

active 

settings. 

<PIN>˽COMMAND

” 

 

1234  SETTINGS 121  services.ionsign.fi 80    internet   /cloud/input/  120 

PIN 

ID 

Device ID 

(1…1 000 000) 

Server 

address 

Operator 

APN 

Update interval 

(

60…30 000 s) 

Server  

path 

Server  

port 

For example JAMAK 
2x(2+1)x0,5mm

2

 

instrumentation cable can 
be used in fieldbus 
wiring. 