Commands Summary
These are the commands accepted by the Ion+ Connect. Note that the commands under the Admin Settings
section will only be accepted if the unit is first unlocked by holding the UNLOCK button on the faceplate until it beeps
twice. To see the current numeric value of an administrator setting, unlock the unit, then send the command with a
question mark at the end of it (e.g.,
pump start?
).
Command
Syntax
Description
ph list
ph list
Responds with list on phone numbers in list
settings
settings
Responds with settings
status
status
Responds with status
pump test
pump test
Run pump test and send result SMS to the phone number
which sent the command only
water
water
Responds with current water level in inches above sensor
temp
temp
Responds with room temperature in degrees Fahrenheit
batt
batt
Responds with Ion+ Connect’s battery’s voltage
ADMIN SETTINGS
name
name Wayne's Basement Sets description of unit location
ph1
ph1 7778889999
Sets first phone number to notify
ph1 clear
Clears phone number
Same as above for
10 phone numbers
alert mode
alert mode alert
Notifies all phone numbers at once - no acknowledgments
alert mode dialer
Notifies phone numbers one at time - acknowledgements*
alert delay
alert delay 5
In alert mode - Sets time in Minutes between sending alerts
In dialer mode - Sets time in Minutes before sending alert to
next ph in list. Allows time for user acknowledgment.
alert suppress
alert suppress 12
In dialer mode - Sets time in Hours to reactivate a previously
acknowledged alarm that has yet to clear
alert suppress 0
In dialer mode - Disable suppression timer feature
(acknowledged alarms stay acknowledged)
alarm delay
alarm delay 15
Sets the time in Seconds that alarm must exist for before
sending alert
pump start
pump start 6.0
Sets the value in inches for level to start the pump running
pump stop
pump stop 2.0
Sets the value in inches for level to stop the pump running
alarm current high
alarm current high 10
Sets the value in Amps that will trigger pump fail alarm
alarm current low
alarm current low 1
Sets the value in amps that will detect pump as being on or
disconnected
alarm power restore
alarm power restore 30
Sets the value in Secs for before power fail clears and
power is deemed to be restored
alarm batt critical
alarm batt critical 3.5
Sets the value in volts for critical low battery threshold (unit
is about to die)
*When the text alert mode is set to “dialer”, simply replying to incoming alerts with a copy of the received alert will
acknowledge it, silencing the alarm and preventing others from receiving the same text alert.