User
Enable access to the configuration functions. Admin password required.
Disconnect
Close the connection with the device and allow to connect to another device.
Change the language.
3.5 Fieldbus communication
3.5.1 Fieldbus support
The safety communication on the Fieldbus interface is supported only in the ISC-B01 control unit.
3.5.2 Communication with the machinery
The Fieldbus makes the following actions possible:
l
to choose from 1 to 32 preset configurations dynamically
l
to read the status of the inputs
l
to control the outputs
l
to mute the sensors
l
to enable the restart signal
For details, see the PROFIsafe communication Reference guide.
3.5.3 Data exchanged through Fieldbus
The following table details the data exchanged through the Fieldbus communication:
WARNING! The system is in alarm if the "control unit status" byte of the "System configuration and
status" module PS2v6 or PS2v4 is different from "0xFF".
Data type
Description
Communication
direction
Safe
SYSTEM STATUS DATA
ISC-B01 control unit:
l
internal status
l
status of each of the four outputs
l
status of each of the two inputs
SBV-01 sensor:
l
status of each detection field (target detected or not) or error status
l
muting status
from the control
unit
Safe
SYSTEM SETTING COMMAND
ISC-B01 control unit:
l
set the ID of the dynamic configuration that shall be activated
l
set the status of each of the four outputs
l
fix the current accelerometer information
l
enable the restart signal
SBV-01 sensor:
l
set the muting status
to the control unit
Safe
DYNAMIC CONFIGURATION STATUS
l
ID of the dynamic configuration currently active
l
signature (CRC32) of the dynamic configuration ID currently active
from the control
unit
3. Get to know SBV System Series
SBV System Series | Instruction manual v1.2 DEC 2021| SAF-UM-SBVBus-en-v1.2 | © 2021 Inxpect SpA
23