Parameter
Min
Max
Default
value
Field of view (for each
sensor)
110°, 50°
110°
Safety working mode (for
each detection field of each
sensor)
Both (default), Always access detection, Always restart prevention
Both
(default)
Restart timeout for each
detection field
0 ms
60 000 ms
10 000 ms
Configuration > Settings > Sensors
Access sensitivity
Normal, High, Very High
Normal
Restart sensitivity
Normal, High, Very High
Normal
Anti-masking
Disabled, Low, Medium, High
High
Anti-rotation around axes
Disabled, Enabled
Enabled
Configuration > Settings > Digital Input-Output
Digital input (for each input) Stop signal, Restart signal, Muting group “N”, Activate dynamic
configuration, Fieldbus controlled, Restart Feedback signal,
Acquisition Trigger*
Note*
: only if the Inxpect Safety application supports the functionality.
Not
configured
Digital output (for each
output)
System diagnostic signal, Muting enable feedback signal, Detection
signal 1, Detection signal 2, Fieldbus controlled
Not
configured
Configuration > Settings > Muting
Group for muting (for each
sensor)
No group, Group 1, Group 2, both
Group 1
Pulse width (for each Input
TYPE)
0 μs (= Period and Phase shift
disabled)
200 μs
2000 μs
0 μs
Period (for each Input TYPE) 200 ms
2000 ms
200 ms
Phase shift (for each Input
TYPE)
0.4 ms
1000 ms
0.4 ms
8.5 Digital input signals
8.5.1 Stop signal
8. Technical references
LBK System BUS | Instruction manual v1.0 SEP 2020 | LBK-System-BUS_instructions_en v1.0 | © 2020 Inxpect SpA
75