Data
type
Description
Communication
direction
Safe
SYSTEM STATUS DATA
ISC-B01 controller:
l
internal status, used to check for errors on the controller
l
real time status of each of the four outputs
l
real time status of each of the two inputs
LBK-S01 sensor:
l
status of each detection field (target detected or not) or error status
l
muting status
from the
controller
Safe
SYSTEM SETTING COMMAND
ISC-B01 controller:
l
set the ID of the dynamic configuration that shall be activated
l
set the status of each of the four outputs
l
fix the current accelerometer information
LBK-S01 sensor:
l
set the muting status
to the controller
Safe
DYNAMIC CONFIGURATION STATUS
l
ID of the dynamic configuration currently active
l
signature (CRC32) of the dynamic configuration ID currently active
from the
controller
Safe
TARGET DATA
Current distance of the targets detected by each sensor connected to the
controller. For each sensor, only the closest target to the sensor is considered.
from the
controller
Unsafe SYSTEM EXTENDED STATUS
ISC-B01 controller:
l
internal status with an extended description of the error condition
LBK-S01 sensor:
l
internal status with an extended description of the error condition
from the
controller
3.6 System configuration
3.6.1 System configuration
The controller parameters have their own default values that can be modified via the Inxpect Safety
application (see "Parameters" on page 74).
3.6.2 Dynamic system configuration
LBK System BUS allows a real-time adjustment of the most important system parameters, providing the
means to switch dynamically among different preset configurations. Via the Inxpect Safety application, once
the first system configuration (default configuration) has been set, it is possible to set up to 31 alternative
presets to allow a dynamic real-time reconfiguration of the monitored area.
The following parameters are part of each of these alternative presets:
l
detection field 1 and 2, for each sensor
l
angular coverage (50° or 110° on the horizontal plane), for each sensor
l
restart timeout, for each detection field of each sensor
l
safety working mode (
Both (default)
,
Always access detection
or
Always restart prevention
), for each
detection field, for each sensor (see "Safety working modes and safety functions" on page 25)
All the remaining system parameters cannot be changed dynamically and are considered static.
3.6.3 Dynamic system configuration activation
The dynamic system configuration can be activated through the digital inputs or the safety Fieldbus (from
3. Get to know LBK System BUS
LBK System BUS | Instruction manual v1.0 SEP 2020 | LBK-System-BUS_instructions_en v1.0 | © 2020 Inxpect SpA
19