IVC-EH-4AD Analog Input Module 

User Manual 

Thanks  for  choosing  the  programmable  logic  controllers  (PLCs)  developed 

and produced by INVT Auto-Control Technology (Shenzhen) Co., Ltd. Before 

using  the  IVC-EH-4AD  series  PLC  products,  read  this  manual  carefully  to 

understand the product features, so that you can install and use the products 

properly and make full use of its abundant functions. 

Note: 

Before  using  the  product,  read  the  operation  instructions  and  precautions 

carefully to prevent accidents. Only trained personnel can install and operate 

the  product,  and  when  installing  and  operating  the  product,  the  operators 

must  strictly  follow  the  related  industrial  safety  specifications  and  the 

precautions  and  special  safety  guide  provided  in  this  manual  to  perform 

operations properly. 

1 Interface description 

1.1 Interface introduction 

Cover  plates  are  provided  for  the  extension  cable  interfaces  and  user 

terminals  of the IVC-EH-4AD module,  as shown in Figure 1-1. You can  see 

the  extension  cable  interfaces  and  user  terminals  after  opening  the  cover 

plates, as shown in Figure 1-2. 

 

 

Figure 1-1 Module appearance 

diagram 

Figure 1-2 Module interface 

diagram 

The  IVC-EH-4AD  module  is  connected  to  the  main  module  through  a  patch 

board,  and  the  extension  modules  are  connected  in  cascade  mode  to 

implement  hard  connection.  For  the  specific  connection  method,  see  the 

connection diagram in Figure 1-3. 

Table 1-1 describes the definition of IVC-EH-4AD user terminals. 

Table 1-1 Definition of IVC-EH-4AD user terminals 

Label 

Description 

24V+ 

Positive pole of the 24 V analog power supply 

24V– 

Negative pole of the 24 V analog power supply 

PG 

Ground terminal 

V1+, V2+, V3+, 

V4+ 

Voltage signal input terminals for channels 1, 2, 3, and 4 

FG 

Shielding ground 

I1+, I2+, I3+, I4+  Current signal input terminals for channels 1, 2, 3, and 4 

VI1–, VI2–, VI3–, 

VI4– 

Common ground terminals for channels 1, 2, 3, and 4 

· 

Empty pin 

Special statement:

 Voltage signals and current signals of a channel cannot 

be input simultaneously. To detect current signals, 

short-circuit

 the voltage 

signal input terminal of the channel to the current signal input terminal. 

1.2 System connection 

IVC-EH-4AD is  applied to IVC3 series PLC systems. It can be connected to 

an  IVC3  series  system  through  hard  connection,  that  is,  inserting  it  into  the 

extension interface  of  any  extension module  of the main module  or  system, 

as shown in Figure 1-3. 

After  the  IVC-EH-4AD  module  is  connected  to  the  system,  its  extension 

interface can also be used to connect another extension module of the IVC3 

series,  such  as  the  I/O  extension  module,  VC-EH-4DA,  IVC-EH-4TC,  or 

another IVC-EH-4AD. 

The  main  module  of  an  IVC3  series  PLC  can  be  extended  with multiple  I/O 

extension  modules  and  special  function  modules.  The  number  of  extension 

modules depends on the power that the module can supply. For details, see 

section  4.7  "Power  supply  specifications"  in  the 

IVC3  Series  PLC  User 

Manual

 

Figure 1-3 Diagram of the connection between IVC-EH-4AD analog 

input modules and the main module 

1.3 Wiring description 

Figure 1-4 shows the user terminal wiring requirements. Pay attention to the 

following seven aspects: 

1.  It is recommended that you connect the analog input by using a shielded 

twisted-pair cable,  and keep the cable  away  from power cables  or  other 

cables that may cause electrical interference. 

2.  If fluctuation occurs in input signals, or external cables cause electrical 

interference, it is recommended that you configure a smoothing capacitor 

(0.1μF to 0.47μF/25V). 

3.  If current input is adopted for a channel, short-circuit the voltage input 

terminal of the channel to the current input terminal. 

4.  If too much electrical interference is caused, connect the shielding ground 

FG to the ground terminal PG of the module. 

5.  Ground the ground terminal PG of the module properly. 

6.  The auxiliary 24 V DC output power supply or any other power supply that 

meets requirements can be used as the analog power supply. 

7.  Do not use the empty pin of the user terminal. 

I1 +

C H 1

2 4 V +

2 4 V -

D C /D C

c o n v e rte

r

A G N D

+5 V

-5 V

P

G

N

D

P G

IV C 2 L -4 A D

D

C

2

4

V

±

1

0

%

6

0

m

A

V 1 +

V I1 -

FG

A G ND

2 5 0

Ω

1 3 0 K

Ω

1 3 0 K

Ω

3 9 0 K

Ω

3 9 0 K

Ω

A G ND

C u r re n t  sig n a l

I4 +

C H 4

V 4 +

V I4 -

FG

A G ND

2 5 0

Ω

1 3 0 K

Ω

1 3 0 K

Ω

3 9 0 K

Ω

3 9 0 K

Ω

A G ND

V o lta g e  s ig n a l

Figure 1-4 IVC-EH-4AD user terminal wiring diagram 

2 Instructions 

2.1 Power supply specifications 

Table 2-1 Power supply specifications 

Item 

Description 

Analog circuit 

24 V DC (-15%–+20%); Max. allowable ripple voltage: 5%; 

50 mA (supplied by the main module or external power 

supply) 

Digital circuit 

5 V DC, 72 mA (supplied by the main module) 