Goodrive350-19 series VFD for crane
Function parameter list
-235-
Function
code
Name
Description
Default
Modify
I/F mode for AM 2 for switching off the output current closed-loop
control. When the output frequency is lower than
the value of this parameter, the current
closed-loop control in the I/F control mode is
enabled; and when the output frequency is
higher than P04.51, the current closed-loop
control in the I/F control mode is disabled.
Setting range: 0.00
–20.00 Hz
P04.50
End frequency for
switching off I/F
mode for motor 1
P04.44
–P00.03
25.00Hz
○
P04.51
End frequency for
switching off I/F
mode for motor 2
P04.49
–P00.03
25.00Hz
○
P04.52
Reverse current
setting in I/F mode
for AM 1
0.0
–200.0%
120.0%
○
P04.53
Reverse current
setting in I/F mode
for AM 2
0.0
–200.0%
120.0%
○
P05 group
––Input terminals
Function
code
Name
Description
Default
Modify
P05.00
HDI input type
0x00
–0x11
Ones place: HDIA input type
0: HDIA is high-speed pulse input
1: HDIA is digital input
Tens place: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
0x00
◎
P05.01
Function of S1
0: No function
1: Run forward
2: Run reversely
3: Three-wire running control
4: Jog forward
5: Jog reversely
6: Coast to stop
1
◎
P05.02
Function of S2
2
◎
P05.03
Function of S3
7
◎
P05.04
Function of S4
0
◎
P05.05 Function of HDIA
0
◎
P05.06 Function of HDIB
0
◎
P05.07
Reserved
0
◎