Goodrive350-19 series VFD for crane
Commissioning guidelines
-128-
5.17.2 Using KTY84
Through an AI terminal
Figure 5-27 Wiring between analog terminals and KTY84
Note: Turn SW2 on the control board to "I" for current output.
Procedure
1. Connect KTY84 according to the figure.
2. Set set P92.22=3 to select KTY84.
3. Set P92.23 (AI detected motor overtemperature protection threshold) and P92.24 (AI detected
motor overtemperature alarm threshold).
4. Check whether P94.20 (AI detected motor temperature) is correct.
Function parameter settings
Function
code
Name
Description
Setting
P92.22
Type of sensor for
AI to detect motor
temperature
3: KTY84
3
P92.23
AI detected motor
overtemperature
protection threshold
0.0
–200.0°C
110.0
P92.24
AI detected motor
overtemperature
pre-alarm threshold
0.0
–200.0°C
90.0
P94.20
AI detected motor
temperature
-20.0
–200.0°C
0.0°C