Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-32-
Function
code
Name
Description
Setting range
Default
P06.15
AO1 output lower
limit
-100.0%
–P06.17
-100.0
–P06.17
0.0%
P06.16
AO1 output
corresponding to
lower limit
-10.00V
–10.00V
-10.00
–10.00
0.00V
P06.17
AO1 output upper
limit
P06.15
–100.0%
P06.15
–100.0
100.0%
P06.18
AO1 output
corresponding to
upper limit
-10.00V
–10.00V
-10.00
–10.00
10.00V
P06.19
AO1 output filter time 0.000
–10.000s
0.000
–10.000
0.000s
P06.20
AO2 output lower
limit
-100.0%
–P06.22
-100.0
–P06.22
0.0%
P06.21
AO2 output
corresponding to
lower limit
-10.00
–10.00V
-10.00
–10.00
0.00V
P06.22
AO2 output upper
limit
P06.20
–100.0%
P06.20
–100.0
100.0%
P06.23
AO2 output
corresponding to
upper limit
-10.00V
–10.00V
-10.00
–10.00
10.00V
P06.24
AO2 output filter time 0.000
–10.000s
0.000
–10.000
0.000s
The function codes define the relationship between the output value and analog output. When the output value exceeds
the allowed range, the output uses the lower limit or upper limit.
When the analog output is current output, 1mA equals 0.5V.
In different cases, the corresponding analog output of 100% of the output value is different. See each application for
detailed information.
-100%
100%
Corresponding
setting
AO
-10V
10V
(20mA)
0
AO1, AO2
(-20mA )
P07 group
––Human-machine interface
Function
code
Name
Description
Setting range
Default
P07.00
User password
0
–65535
0
–65535
0
When you set the function code to a non-zero number, password protection is enabled.
If you set the function code to 00000, the previous user password is cleared and password protection is disabled.
After the user password is set and takes effect, you cannot enter the parameter menu if you enter an incorrect password.