Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-28-
Function
code
Name
Description
Setting range
Default
the function code. The changes on
the feedback angle will effect the
current waveform. It is not
recommended to modify this
parameter. The feedback angle is
set properly by default.
(Valid only for the six-pulse rectifier)
P03.39
–
P03.40
Reserved
P05 group
––Input terminals
Function
code
Name
Description
Setting range
Default
P05.01
Digital input terminal
polarity
0x0
–0xF
0x0
–0xF
0x0
The function code is used to select input terminal polarity.
When a bit is 0, the input terminal is positive; when a bit is 1, the input terminal is negative.
BIT3
BIT2
BIT1
BIT0
S4
S3
S2
S1
Function
code
Name
Description
Setting range
Default
P05.03
Digital input filter time
0.000
–1.000s
0.000
–1.000
0.000s
The function code is used to set the filter time for S1
–S4. In strong interference cases, increase the value to avoid
maloperation.
Function
code
Name
Description
Setting range
Default
P05.04
Function of S1
terminal
0: No function
1: Run
2: Reset faults
3: External fault
4: Reserved
5: Enable
6
–12: Reserved
13: Clear accumulative electricity
consumption
14: Keep accumulative electricity
consumption
15: Reserved
0
–15
1
P05.05
Function of S2
terminal
2
P05.06
Function of S3
terminal
0
P05.07
Function of S4
terminal
0
Terminal input is described as follows:
Setting
Function
Description
0
No function
The PWM rectifier does not act even if with signal input. Set unused
terminals to "no function” to avoid misaction.
1
Run
External terminals are used to control PWM rectifier running.
2
Fault reset
External fault reset function, same as the reset function of the
STOP/RST key on the keypad. You can use this function to reset
faults remotely.