P02 group
––Reserved parameters
Function code
Name
Description
Setting range
Default
P02.00
–P02.07
Reserved
P03 group
––Control parameters
Function
code
Name
Description
Setting
range
Default
P03.06
Positive limit on active current
(rectification)
0.0
–200.0% (of the rectifier rated
current)
0.0
–200.0% 150.0%
P03.07
Negative limit on active current
(feedback)
0.0
–200.0% (of the rectifier rated
current)
0.0
–200.0% 150.0%
P03.08
Positive limit on reactive current
(rectification)
0.0
–200.0% (of the rectifier rated
current)
0.0
–200.0% 150.0%
P03.09
Negative limit on reactive current
(feedback)
0.0
–200.0% (of the rectifier rated
current)
0.0
–200.0% 150.0%
P03.10
Max. current setting
0
–250.0% (of the rectifier rated
current)
0.0
–250.0% 200.0%
P03.06 indicates the maximum active current at rectifier output.
P03.07 indicates the maximum active current at energy feedback.
P03.08 indicates the maximum reactive current at rectifier output.
P03.09 indicates the maximum reactive current at energy feedback.
P03.10 indicates the max. current output limited by the rectifier automatic current limit function.
Function
code
Name
Description
Setting range
Default
P03.11
Voltage-loop
proportional
coefficient 1
0.001
–30.000
0.001
–30.000
2.000
P03.12
Voltage-loop integral
coefficient 1
0.01
–300.00
0.01
–300.00
20.00
P03.13
Voltage-loop
proportional
coefficient 2
0.001
–30.000
0.001
–30.000
5.500
P03.14
Voltage-loop integral
coefficient 2
0.01
–300.00
0.01
–300.00
10.00
P03.15
PI parameter
switching voltage
0.01
–30.00V
0.01
–30.000
10.00V
The absolute value of the difference between the DC voltage setting for the PI regulation in the voltage loop and the DC
voltage feedback is ∆.
When ∆ is less than the PI parameter switching voltage, PI parameter 1 is used. When ∆ is equal to or greater than the PI
parameter switching voltage, PI parameter 2 is used.
Function
code
Name
Description
Setting range
Default
P03.16
Bus voltage filter
coefficient
0
–1.000s
0
–1.000s
0.000s
The function code indicates the bus voltage displayed on the keypad.