Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-121-
Function
code
Name
Description
Setting range
Default
P13.05
VF oscillation control
method/High frequency
overlay frequency
(reserved)
0: R active
1: Reactive
2: Active
0
–2
0
P13.06
High frequency
superimposed voltage
0.0
–300.0% (of the motor rated
voltage)
0.0
–300.0
50.0%
P13.07
Frequency drop rate during
current limit
0.0
–400.0
0.0
–400.0
0.0
P13.08
Control parameter 1
0
–65535
0
–65535
0
P13.09
Control parameter 2
0
–655.35
0
–655.35
2.00
P13.10
Angle compensation
0
–6553.5
0
–6553.5
0
P13.11
Maladjustment detection
time
0.0
–10.0s
0.0
–10.0
0.5s
P13.12
High frequency
compensation coefficient
0
–100.0%
0
–100.0
0.0%
P13.13
Short-circuit braking
current
0.0
–150.0% (of the VFD rated
current)
0.0
–150.0
0.0%
P13.14
Hold time of short-circuit
braking for start
0.00
–50.00s
0.00
–50.00
0.00s
P13.15
Hold time of short-circuit
braking for stop
0.00
–50.00s
0.00
–50.00
0.00s
P13.16
SM brake component
enabling
0
–1
0
–1
0
P13.17
SM brake component
enabling threshold voltage
200.0
–6000.0V
200.0
–6000.0
Model
depended
P13.18
SM brake component
conduction time
0.000
–4.000s
0.000
–4.000
1.000
P13.19
–
P13.20
Reserved
P13.21
Start frequency of
mal-adjustment fault
determination
0.00
–50.00Hz
0.00
–50.00
5.00Hz
P13.22
Mal-adjustment fault
detection deviation angle
0.00
–359.99
0.00
–359.99
36.00
P13.23
Enabling protection against
runaway fault
0: Invalid
1: Valid
0
–1
0
P13.24
–
P13.25
Reserved
When the counter-emf of SM is high, a new synchronous machine brake component is required to ensure that the
counter-emf does not lead to bus voltage overvoltage in case of emergency stop and it can be controlled via P13.16 and
P13.17.
P14 group
––Serial communication
Function
code
Name
Description
Setting range
Default
P14.00
Local communication
address
1
–247; 0 indicates a broadcast
address
1
–247
1