Goodrive350 series high-performance multifunction VFD
Installation guidelines
-28-
Terminal
Terminal name
Function description
380V 37kW
and lower
380V
45
–110kW
(inclusive)
380V 132kW and
higher
660V
R, S, T
Main circuit power input
3PH AC input terminals,
connected to the grid
U, V, W
VFD output
3PH AC output terminals,
connected to the motor
P1
Not available Not available DC reactor terminal 1 P1 and (+) connect to the
external DC reactor.
(+) and (-) connect to the
external braking unit.
PB and (+) connect to external
braking resistor terminal
(+)
Braking resistor
terminal 1
Braking unit
terminal 1
DC reactor terminal 2,
Braking unit terminal 1
(-)
/
Braking unit terminal 2
PB
Braking resistor
terminal 2
Not available
PE
Safety protection grounding terminal
Grounding terminal for safety
protection. Each VFD carries
two PE terminals and proper
grounding is required.
A1, A2
Not available
For 660V models:
220V control power
supply terminals
Terminals for connection to
external 220V power supply.
Note:
Do not use asymmetrical motor cables. If there is a symmetrical grounding conductor in the
motor cable besides the conductive shielded layer, ground the grounding conductor on the VFD
end and motor end.
Braking resistor, braking unit and DC reactor are optional parts.
Route the motor cable, input power cable and control cables separately.
"Not available" means this terminal is not provided for external connection.
GD series VFDs cannot share the DC bus with CH series VFDs.
When sharing the DC bus, the VFDs must be the same in power and must be simultaneously
powered on or off.
In shared DC bus running mode, current balance on the VFD input side must be considered
during wiring, and equalizing reactors are recommended to be configured.
4.3.4 Wiring procedure of the main circuit terminals
1.
Connect the grounding line of the input power cable to the grounding terminal (PE) of the VFD,
and connect the 3PH input cable to R, S and T terminals and tighten up.
2.
Connect the grounding line of the motor cable to the grounding terminal of the VFD, and connect
3PH motor cable to U, V and W terminals and tighten up.
3.
Connect the braking resistor which carries cables to the designated position.