Goodrive350 series high-performance multifunction VFD
Function parameter list
-265-
Function
code
Name
Description
Default
value
Modify
4: 48+24+60
5: 60+48+60
6: 72+24+60
7: 84+24+60
8: 96+96+96
Tens place: Card that communicates with the
programmable card through PZD (valid only when
the ones place of P27.26 is 5)
0: DP card
1: CANopen card
2: PN card
Note:
P27.26 can be changed at any time, but the
change will only take effect after the re-power on.
P27.27
Programmable
card save
function at power
failure
0
–1
0: Disable
1: Enable
1
◎
P28
––
Master/slave control functions
Function
code
Name
Description
Default Modify
P28.00
Master/slave
mode
0: Master/slave control is invalid
1: The local machine is a master
2: The local machine is a slave
0
◎
P28.01
Master/slave
communication
data selection
0: CAN
1: Reserved
0
◎
P28.02
Master/slave
control mode
0x000
–0x112
Ones place: Master/slave running mode selection
0: Master/slave mode 0
(The master and slave adopt speed control and
maintain the power balance by droop control)
1: Master/slave mode 1
(The master and slave must be in the same type of
vector control mode. The master is speed control,
and the slave will be forced to be in the torque
control mode.
2: Master/slave mode 2
Start in the slave first speed mode (master/slave
mode 0) and then switch to torque mode at a
certain frequency point (master/slave mode 1)
0x001
◎