GD310-UL series VFD
Function parameter
-80-
Function
code
Name
Description
Default
value
Modify
P07.49 Running frequency at the last but one fault
0.00Hz
●
P07.50 Output voltage at the last but one faults
0.00Hz
●
P07.51 Output current at the last but one faults
0V
●
P07.52 Output current at the last but one fault
0.0A
●
P07.53 Bus voltage at the last but one fault
0.0V
●
P07.54 The max temperature at the last but one fault
0.0°C
●
P07.55 Input terminals state at the last but one fault
0
●
P07.56 Output terminals state at the last but one fault
0
●
P08 Group Enhanced function
Function
code
Name
Description
Default
value
Modify
P08.00
ACC time 2
See P00.11 and P00.12 for detailed definition.
Goodrive310-UL series define four groups of
ACC/DEC time which can be selected by P5 group.
The first group of ACC/DEC time is the factory
default one.
Setting range: 0.0
–3600.0s
Depend
on model
○
P08.01
DEC time 2
Depend
on model
○
P08.02
ACC time 3
Depend
on model
○
P08.03
DEC time 3
Depend
on model
○
P08.04
ACC time 4
Depend
on model
○
P08.05
DEC time 4
Depend
on model
○
P08.06
Jogging
frequency
This parameter is used to define the reference
frequency during jogging.
Setting range: 0.00Hz
–P00.03 (the max frequency)
5.00Hz
○
P08.07
Jogging ACC
time
The jogging ACC time means the time needed if the
VFD runs from 0Hz to the max Frequency.
The jogging DEC time means the time needed if the
VFD goes from the max frequency (P0.03) to 0Hz.
Setting range: 0.0
–3600.0s
Depend
on model
○
P08.08
Jogging DEC
time
Depend
on model
○
P08.09
Jumping
frequency 1
When the set frequency is in the range of jumping
frequency, the VFD will run at the edge of the
jumping frequency.
The VFD can avoid the mechanical resonance point
by setting the jumping frequency. The VFD can set
three jumping frequency. But this function will be
invalid if all jumping points are 0.
0.00Hz
○
P08.10
Jumping
frequency
range 1
0.00Hz
○
P08.11
Jumping
frequency 2
0.00Hz
○