GD310-UL series VFD
Function parameter
-54-
Function
code
Name
Description
Default
value
Modify
coefficient
coefficient.
So, the bigger the value of K is, the smaller the value
of M is. When M =116%, the fault will be reported
after 1 hour, when M =200%, the fault will be
reported after 1 minute, when M>=400%, the fault
will be reported instantly.
Times of motor overload
1 hour
1 minute
116%
200%
Setting range: 20.0%
–120.0%
P02.28
Correction
coefficient of
motor 1 power
Correct the power displaying of motor 1.
Only impact the displaying value other than the
control performance of the VFD.
Setting range: 0.00
–3.00
1.00
●
P02.29
Parameter
display of
motor 1
0: Display according to the motor type
1: Display all
0
●
P03 Group Vector control
Function
code
Name
Description
Default
value
Modify
P03.00
Speed loop
proportional
gain1
The parameters P03.00
–P03.05 only apply to vector
control mode. Below the switching frequency
1(P03.02), the speed loop PI parameters are: P03.00
and P03.01. Above the switching frequency
2(P03.05), the speed loop PI parameters are: P03.03
and P03.04. PI parameters are gained according to
the linear change of two groups of parameters. It is
shown as below:
Output frequency
P03.00, P03.01
P03.02
P03.05
P03.03, P03.04
PI parameter
20.0
○
P03.01
Speed loop
integral time1
0.200s
○
P03.02
Low switching
frequency
5.00Hz
○
P03.03
Speed loop
proportional
gain 2
20.0
○
P03.04
Speed loop
integral time 2
0.200s
○
P03.05
High switching
frequency
10.00Hz
○