GD310-UL series VFD
Basic operation instruction
-142-
7.9 Analog input
Goodrive310-UL series VFDs have three analog input terminals and 1 high-speed pulse input
terminals (of which, AI1 and AI2 are 0
–10V/0–20mA and Al can select voltage input or current input by
J3, AI2 can select voltage input or current input by J4 and AI3 is for -10
–10V ) as the standard
configuration. The inputs can be filtered and the maximum and minimum values can be adjusted.
AI1
AI3
HDI
P05.32
P05.33
P05.34
P05.35
P05.42
P05.43
P05.44
P05.45
P05.46
P05.47
P05.50
P05.51
P05.52
P05.53
P05.48
P05.36
P05.54
P17.19
P17.21
P17.22
AI2
P05.37
P05.38
P05.39
P05.40
P05.41
P17.20
P05.00
(
HDI input type selection
)
0
1
1
2
0
P05.49
(
HDI high speed pulse input function selection
)
AI1 input voltage
AI2 input voltage
AI3 input voltage
HDI input frequency
AI3
AI1/AI2/HDI
P05.00
0: HDI is high speed pulse input
1: HDI is switch input
P05.49
0: frequency setting input
1: counter input
2: length counter input
Analog curve input setting
Analog input filter
Related parameters list:
Function
code
Name
Description
Default
value
P05.00
HDI input selection
0: High pulse input
1: Digital input
0
P05.32
Lower limit of AI1
0.00V
–P05.34
0.00V
P05.33
Corresponding setting of the lower
limit of AI1
-100.0%
–100.0%
0.0%
P05.34
Upper limit of AI1
P05.32
–10.00V
10.00V
P05.35
Corresponding setting of the upper
limit of AI1
-100.0%
–100.0%
100.0%
P05.36
AI1 input filter time
0.000s
–10.000s
0.100s
P05.37
Lower limit of AI2
0.00V
–P05.39
0.00V
P05.38
Corresponding setting of the lower
limit of AI2
-100.0%
–100.0%
0.0%
P05.39
Upper limit of AI2
P05.37
–10.00V
10.00V
P05.40
Corresponding setting of
the upper limit of AI2
-100.0%
–100.0%
100.0%
Содержание GD310-011P-4-UL
Страница 1: ......
Страница 269: ...6 6 0 0 1 0 0 3 9 3 ...