GD310-UL series VFD
Basic operation instruction
-137-
Function
code
Name
Description
Default value
P01.19
Action if running
frequency< lower limit
frequency (valid >0)
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
0
P01.20
Hibernation restore delay
time
0.0
–3600.0s (valid when P01.19=2)
0.0s
P01.21
Restart after power off
0: Disable
1: Enable
0
P01.22
The waiting time of restart
after power off
0.0
–3600.0s (valid when P01.21=1)
1.0s
P01.23
Start delay time
0.0
–60.0s
0.0s
P05.01
–P
05.09
Digital input function
selection
1: Forward rotation operation
2: Reverse rotation operation
4: Forward rotation jogging
5: Reverse rotation jogging
6: Coast to stop
7: Fault reset
8: Operation pause
21: ACC/DEC time option 1
22: ACC/DEC time option 2
30: ACC/DEC prohibition
P08.06
Jogging frequency
0.00Hz
–P00.03 (the max frequency)
5.00Hz
P08.07
Jogging ACC time
0.0
–3600.0s
Depend on model
P08.08
Jogging DEC time
0.0
–3600.0s
Depend on model
P08.00
ACC time 2
0.0
–3600.0s
Depend on model
P08.01
DEC time 2
0.0
–3600.0s
Depend on model
P08.02
ACC time 3
0.0
–3600.0s
Depend on model
P08.03
DEC time 3
0.0
–3600.0s
Depend on model
P08.04
ACC time 4
0.0
–3600.0s
Depend on model
P08.05
DEC time 4
0.0
–3600.0s
Depend on model
P08.28
Fault reset times
0
–10
0
P08.29
Interval time of automatic
fault reset
0.1
–3600.0s
1.0s
7.8 Frequency setting
Goodrive310-UL series VFDs can set the frequency by various means. The given channel can be
divided into main given channel and assistant given channel.
There are two main given channels: A frequency given channel and B frequency given channel.