GD200A series VFD
Fault tracking
-124-
Checking part
Checking item
Checking
method
Criterion
Ensure there is no weeping
and distortion to the capacitors.
Visual
examination
or
estimate
the
usage
time
according to the
maintenance
information
NA
Cooling
system
Cooling fan
Estimate whether there is
abnormal noise and vibration.
Hearing
and
Visual
examination
or
rotate with hand
Stable rotation
Estimate there is no losses
screw.
Tighten up
NA
Ensure
there
is
no
color-changing
caused
by
overheating.
Visual
examination
or
estimate
the
usage
time
according to the
maintenance
information
NA
Ventilating
duct
Ensure whether there is stuff or
foreign objection in the cooling
fan, air vent.
Visual
examination
NA
Consult the local service representative for more details on the maintenance. Visit the official
website of INVT http: //www.invt.com and choose
Service
.
8.8.2 Cooling fan
The VFD's cooling fan has a minimum life span of 25,000 operating hours. The actual life span
depends on the VFD usage and ambient temperature.
The operating hours can be found through P07.14 (accumulative hours of the VFD).
Fan failure can be predicted by the increasing noise from the fan bearings. If the VFD is operated in
a critical part of a process, fan replacement is recommended once these symptoms appear.
Replacement fans are available from INVT.
8.8.2.1 Replacing the cooling fan
Read and follow the instructions in chapter 1 Safety precautions. Ignoring the
instructions would cause physical injury or death, or damage to the equipment.