Goodrive20-EU series VFD
Function parameters
36
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00.08
B frequency
command
reference
selection
0: Maximum output frequency, 100% of B
frequency setting corresponds to the maximum
output frequency
1: A frequency command, 100% of B frequency
setting corresponds to the maximum output
frequency. Select this setting if it needs to adjust
on the base of A frequency command.
0
○
P00.09
Combination of
the setting
source
0: A, the current frequency setting is A frequency
command
1: B, the current frequency setting is B frequency
command
2: A+B, the current frequency setting is A
frequency c B frequency command
3: A-B, the current frequency setting is A
frequency command - B frequency command
4: Max. (A, B): The bigger one between A
frequency command and B frequency is the set
frequency.
5: Min. (A, B): The lower one between A
frequency command and B frequency is the set
frequency.
Note:
The combination manner can be shifted by
P05 (terminal function)
0
○
P00.10
Keypad set
frequency
When A and B frequency commands are
selected as "keypad setting", this parameter will
be the initial value of VFD reference frequency
Setting range: 0.00 Hz
–P00.03 (the max.
frequency)
50.00Hz
○
P00.11
Acceleration
time 1
Acceleration time means the time needed for the
VFD to speed up from 0Hz to the maximum
output frequency (P00.03).
Deceleration time means the time needed if the
VFD speeds down from the maximum output
frequency (P00.03) to 0Hz.
Goodrive20-EU series VFDs have four groups of
acceleration/deceleration time which can be
selected by P05. The default
Depend
on
model
○
P00.12
Deceleration
time 1
Depend
on
model
○