Goodrive10 Series Mini VFD
Function parameters
-49-
Function
code
Name
Description
Default Modify
the motor)
9: Output torque
10: AI1 input
11: AI2 input
14: Value 1 set through Modbus communication
15: Value 2 set through Modbus communication
P06.17
Lower limit
of AO output
The function codes define the relationship
between the output value and analog output.
When the output value exceeds the allowed
range, the output uses the lower limit or upper
limit.
When the analog output is current output, 1 mA
equals to 0.5 V.
In different cases, the corresponding analog
output of 100% of the output value is different.
10V (20mA)
0.0%
100.0%
AO
Corresponding
setting
Setting range of P06.17 0.0%
–P06.19
Setting range of P06.18 0.00V
–10.00V
Setting range of P06.19 P06.17
–100.0%
Setting range of P06.20 0.00V
–10.00V
Setting range of P06.21 0.000s
–10.000s
0.0%
○
P06.18
Correspondi
ng AO
output to the
lower limit
0.00V
○
P06.19
Upper limit
of AO output
100.0%
○
P06.20
The
correspondi
ng AO
output to the
upper limit
10.00V
○
P06.21
AO output
filter time
0.000s
○
P07 group HMI
Function
code
Name
Description
Default Modify
P07.00
User
password
0
–65535
When you set the function code to a non-zero
number, password protection is enabled.
If you set the function code to 00000, the previous
user password is cleared and password protection
is disabled.
After the user password is set and takes effect,
0
○